User Manual 5.1-1 (2018-09) 25
Subject to change
Series FK92K
Minimum spacings [mm]
G
P
R
with walls
without with
Wall thickness metal studs
< 50 mm*
)
≥
160
≥
70
≥
70
≥
70
≥
50 mm
≥
160
≥
50
≥
40
≥
35
*
)
Wall thicknesses < 50 mm must be
increased on all sides to
≥
60 mm with a
width of 70 mm.
FK90K fire dampers
Installation in shaft walls with and without metal studs (1)
•
Width and height of the shaft walls:
For the restricted dimensions, refer to the general building
authority test certificates (AbP). They depend on the size
of the framework profiles or the boundary fixations, and
the type and thickness of the cladding.
•
Dimensions of installation openings b x h
⇒
see page 17
•
If the span of the framework is smaller than the width of
the fire damper (with a horizontal axis, or height with a
Installation in shaft walls with cladding on one
side, with or without metal studs
Types of metal stud walls with cladding
⇒
see pages 17 and 18
Single or multi-layer
wall cladding
If W ˂ 50 mm
add min. 60 mm
Operation side
Butt joint
FK90K casing
corner
bracket
Operation side
FK90K casing
FK90K
corner bracket
Butt joint
FK90K casing
FK90K casing
Operation side
Operation side
Butt joint
corner
bracket
Installation with
short spacings
Cross-sections A-A
Connections
to rigid walls, ceilings, floors
Operation side
FK90K
corner bracket
Butt joint
FK90K casing
Installation with butt joints s
≤
2
to 5 mm
Filling with gypsum joint filler
For
infor-
mation of
proper filling of
joints
⇒
see pages 17, 21
Drywall screws
Fill butt joints
with gypsum
joint filler
Cross-sections A-A on the left
show the
installation of FK90K fire dampers with
the operation side on the wall side with
cladding.
Cross-sections A-A on the right
show
the installation of FK90K fire dampers
with the operation side on the profile side
of the wall without cladding. The profiles
of the circumferential frame must be com-
pletely filled to a height of at least 70
mm
with strips of wall cladding material, or
with construction boards made from calci-
um silicate,
≥
500 kg/m³. FK90K brackets
must be attached.
FK90K angle brackets can be shortened
by max. 34 mm in order to maintain the
minimum spacings.
⇒
see page 20
When
installing
FK90K fire dampers
with the
operation side
on the unclad-
ded wall side (metal stud side), the
pro-
files, which are circumferential at the
rear, must be filled
with wall cladding
materials.
⇒
see cross-sections A-A, pages 25, 26
Seal gap with
gypsum joint filler
FK90K casing
Bay rail for stiffening
with severed support
Additional
all-round
cladding
Operation side
Butt joint
corner
bracket
Joints
should be filled according to
standard practice in wall construction.
Fire resistance period in minutes
30
60
90
Shaft walls made of wall
boards, at least 2-layer
with metal studs
90
without metal studs
40
Metal studs according
to AbP
Width
Height
with
unlimited
according to AbP
without
according to general building
authority test certificates
(AbP) and limited to
≤
2.5 m
according to general
building authority test
certificates (AbP)
The
minimum thicknesses W [mm]
shown opposite
are required for installing the FK90K fire dampers:
vertical axis), the side profiles must be fitted with a 500
mm
excess length. If smaller dimensions are available, then
the side profiles must be butted up against the connection
profiles and secured as usual for this type of wall. Stud profiles
(supports) can replace side profiles.
•
For FK90K fire dampers with dimensions within the span of
the framework, the bay rails should be connected to the stud
profiles according to standard practice in wall construction.
•
Walls without framework require laterally adjacent rigid walls
with angle profiles, onto which the freely spanned single-layer
or multi-layer wall cladding and extended bay rails of the
circumferential frame of the FK90K fire dampers should be
attached.
•
Securing using 2-way crimping
⇒
see page 17