User Manual 5.1-1 (2018-09) 24
Subject to change
Series FK92K
FK90K fire dampers
Installation in metal stud walls (3c) Sliding ceiling connection
All dimensions in mm
•
Installation subframes ER5 must match the web
height S I of the metal studs I, whose profiles should
have the corresponding stud profile depths.
•
The metal studs II contain a recess that is framed by
the wall profiles. Accordingly, the strips of wall clad-
ding material (e.g. plasterboard) attached to the ceil-
ing are severed and sealed at the front (section C-C).
•
The profiles surrounding the recess on the metal
studs II have reveals made from 30-mm-thick calcium
silicate boards. These are guided up to the ceiling
leaving a gap f for the drop (section B-B) and attached
to the metal stud profiles using drywall screws at
≤ 200 mm centres.
•
If the metal studs have claddings on both sides, then
the sliding joint for the connection collar of the installa-
tion subframe ER5 will lie between cladding I and the
reveal attached to cladding II (section B-B).
•
Joints should be filled as usual for this type of wall.
UW - profile
B
Sliding ceiling
connection based on
wall specifications
f
C
C
≥
02
≥
f
30
f
B
A
A
Dowel*
Suspension*
Lining k
*
)
Supplied
together with
installation
subframe
ER5.
Sliding ceiling
connection based on
wall specifications
Span without intermediate support
Span
Intermediate support
Drywall screws
( 200 mm spacing)
≤
(B + 107)
+2
f
03
Reveal,
calcium silicate,
≥
500 kg/m³
UW profile
CW profile
UW profile
30
A
Wall cladding II
UW profile
A
B
B
C
C
f
≥
02
≥
f
Auxiliary support
(as required)
Span
B + 165
S I or S II
Spacing
if present
S I or S II
Spacing
if present
Wall
cladding I
Sliding joint for
connection
collar ER5
Drywall screws
(
≤
200 mm spacing)
Wall cladding II
Reveal
Wall
cladding I
Drywall screws
Reveal
Wall cladding II
(≤ 200 mm spacing)
Sliding joint for
connection
collar ER5
Installation in double-studded walls
•
Directly underneath ceilings
•
with lining for spacing of
≤
80 mm from ceilings
Section C-C
Section B-B
shown without
connection collar
Section C-C
Section A-A
115
Suspensions*
ER5
Connection collar
Reveal, 30 mm thick
(Calcium silicate,
500 kg/m³)
Stud profile I
50 to 125 mm
Wall cladding I
UW profile
86
76
110
Wall cladding II
Stud profile II
Spacing if present
W
S I
S II
Drywall screws
( 200 mm spacing)
f
f
Dowel*
Ceiling connection
profile (UW profile),
150 mm long
Section A-A
Section B - B
shown without
connection collar
•
The installation of
FK90K fire dampers
is in principle
unchanged.
⇒
see page 23