background image

5

14306499.01 02/2019 EN

WIKA operating instructions, pressure switch, high adjustability of switch differential, model PSM-700

5.3  Electrical mounting

Integration of the pressure switch into the installation

Depending on the load characteristics, additional protective measures, e.g. for motor 

protection, may be required.

DANGER!

Danger to life caused by electric current

Upon contact with live parts, there is a direct danger to life.

 

The instrument may only be installed and mounted by skilled personnel.

Switch off the load circuit before starting work and secure against being switched on 

unauthorised.

Cable preparation

The cable gland(s) used must be suitable for achieving an IP66 ingress protection. Size 

the connecting cables for the largest current strength in the circuits and ensure sufficient 

UV resistance and mechanical stability.

Recommendation: 4-wire cable with conductor cross-section of 0.5 ... 2.5 mm² 

(AWG 20 ... 14). Fit wire ends with end splices. Conductor cross-section for end splices 

with plastic sleeve  ≤ 1.0 mm² and for end splices without plastic sleeve ≤ 1.5 mm².

Grounding

Include the ground connection in the inside of the instrument into the grounding concept 

of the installation. Maximum conductor cross-section 4 mm².

Clamping the cable

6.  Faults

CAUTION!

Physical injuries and damage to property and the environment

If faults cannot be eliminated by means of the listed measures, the instrument 

must be taken out of operation immediately.

 

Ensure that there is no pressure in the instrument and that the load circuit 

is switched off. Protect against being put into operation accidentally.

 

Contact the manufacturer.

 

If a return is needed, please follow the instructions given in chapter 8.2 

“Return”.

WARNING!

Physical injuries and damage to property and the environment caused 

by media

Upon contact with hazardous media, harmful media (e.g. corrosive, toxic, 

carcinogenic), and also with refrigeration plants and compressors, there is a 

danger of physical injuries and damage to property and the environment.

Should a failure occur, aggressive media with extremely high temperature and 

under high pressure or vacuum may be present at the instrument.

 

For these media, in addition to all standard regulations, the appropriate 

existing codes or regulations must also be followed.

For further information see chapter 1 “General information”.

Faults

Causes

Measures

Contact is not switching 

in accordance with the 

specification at the set 

switch point/reset point

Electrical connection 

is interrupted.

Carry out a continuity test on the electri-

cal connection lines.

Wiring error, e.g. 

short-circuit

Check the pin assignment and correct it 

if necessary

Electrical load 

unsuitable.

Maintain the permissible electrical loads.

Contact contami-

nated.

Replace instrument

Switch differential 

greater than the 

switch point.

Carry out switch point setting with 

matching test assembly, see chapter 

5.2.

Vibrations

Decouple the instrument mechanically.

Short-circuit

Moisture in the 

instrument.

Only use in ambient conditions for which 

the ingress protection is suitable.

Contact chatter 

(repeated, short-

duration opening and 

closing).

Vibrations

Decouple the instrument mechanically.

1.  Remove 4 screws and open cover

2.  Remove the cover(s) of the electrical 

connection(s)

3.  Fit suitable cable gland(s) and feed in 

the cable

4.  Carry out the terminal assignment 

according to the switching function, 

tightening torque: Approx. 0.4 ... 0.5 Nm

5.  Close the cover again and fix it with the 

4 supplied screws.

5.4  Switch point setting

For an exact setting of the switch point, a test assembly with pressure generation and 

pressure reference is needed. This test assembly can, for example, be realised with a 

model CPG1500 precision digital pressure gauge and a model CPP30 hand test pump 

(not shown).

1.  Connect the model PSM-700 pressure switch, pressure reference and pressure 

generation to a common pressure system.

2.  Ensure that the switch point setting does not switch any loads on or off by mistake. 

For visualisation of the switching function, an equivalent circuit, e.g. with a light bulb, 

is recommended.

3.  Drive slowly towards the required switch point pressure with the pressure generation 

and pressure reference. Depending on the definition of the switch point, this must be 

carried out on rising/falling pressure.

- If the instrument switches 

before

 the required switch point is reached, the switch 

point setting must be turned clockwise (+) with the socket wrench.

- If the instrument switches 

after

 the required switch point is reached, the switch 

point setting must be turned anticlockwise (-) with the socket wrench.

After each correction, release/build up the pressure and repeat this procedure until 

the switch point is set correctly.

For instruments with adjustable switch differential directly in the connection, follow the 

instructions in the next chapter.

Figure 1: Instrument mounting at the test assembly (also see 5.2 “Mechanical mounting”)

Figure 2: Screwing out the locking plate

Figure 3: Switch point setting

Figure 1

Figure 3

Figure 2

Hold instrument

Screw in and seal the process 

connection

Содержание PSM-700

Страница 1: ...ty and environmental criteria during production Our management systems are certified to ISO 9001 These operating instructions contain important information on handling the instru ment Working safely requires that all safety instructions and work instructions are observed Observe the relevant local accident prevention regulations and general safety regulations for the instrument s range of use The ...

Страница 2: ... of any damage caused by using the product contrary to its intended use non compliance with these operating instructions assignment of insufficiently qualified skilled personnel or unauthorised modifications to the instrument The general terms and conditions contained in the sales documentation shall apply Subject to technical modifications Further information Internet address www wika de www wika...

Страница 3: ... that lie within its technical performance limits e g max ambient temperature material compatibility For performance limits see chapter 9 Specifications This instrument is not permitted to be used in hazardous areas The instrument has been designed and built solely for the intended use described here and may only be used accordingly The manufacturer shall not be liable for claims of any type based...

Страница 4: ...its original packaging in a location that fulfils the conditions listed above 5 Commissioning operation Before installation commissioning and operation ensure that the appropriate instru ment has been selected in terms of design and specific measuring conditions Tools 6 5 mm socket wrench cross head screwdreiver 20 mm open ended spanner 6 mm Allen key 5 1 Requirements at the measuring point The pr...

Страница 5: ...operty and the environment Should a failure occur aggressive media with extremely high temperature and under high pressure or vacuum may be present at the instrument For these media in addition to all standard regulations the appropriate existing codes or regulations must also be followed 1 Remove 4 screws and open cover 2 Remove the cover s of the electrical connection s 3 Fit suitable cable glan...

Страница 6: ...ch point Carry out switch point setting with matching test assembly see chapter 5 2 Vibrations Decouple the instrument mechanically Short circuit Moisture in the instrument Only use in ambient conditions for which the ingress protection is suitable Contact chatter repeated short duration opening and closing Vibrations Decouple the instrument mechanically 5 5 Setting of the switch differential opti...

Страница 7: ...elow 1 Before cleaning correctly disconnect the instrument from the pressure supply and switch the load circuit off 2 Use the requisite protective equipment 3 Clean the instrument with a moist cloth Electrical connections must not come into contact with moisture CAUTION Damage to the instrument Improper cleaning may lead to damage to the instrument Do not use any aggressive cleaning agents Do not ...

Страница 8: ...s I per IEC 61010 1 2010 case grounded with protective conductor overvoltage category II pollution degree 2 Contact version Switch type Electrical rating AC Electrical rating DC Resistive load Inductive load Resistive load Inductive load 125 V 250 V 125 V 250 V 30 V 125 V 250 V 30 V 125 V 250 V Switch differential Fixed SPDT 10 A 10 A 10 A 10 A 2 A 0 4 A 0 2 A 1 A 0 03 A 0 02 A DPDT 15 A 10 A 10 A...

Отзывы: