WIKA operating instructions, pressure switch, high adjustability of switch differential, model PSM-700

WIKA operating instructions, pressure switch, high adjustability of switch differential, model PSM-700

Faults

Causes

Measures

Switching status 

remains unchanged 

despite reaching the 

switch point/reset point.

Error with switch point 

setting.

Carry out switch point setting with 

matching test assembly.

Contacts defective 

(e.g. fused contact 

zone).

Replace instrument. Before recommis-

sioning the new instrument, provide a 

protective circuit for the contact.

Pressure port 

blocked.

Replace instrument.

Leakage

Carry out a leak test. Seal the process 

connection or replace the instrument.

For the exchange of the instrument chapters 8 “Dismounting, return and disposal” and 5 

“Commissioning, operation” must be observed.

7.  Maintenance and cleaning

7.1  Maintenance

The instruments are maintenance-free.

The switch point setting must be checked after 6 months. Carry out switch point setting 

with matching test assembly, see chapter 5.2.

Carry out the check with slow rate of change of pressure in the desired pressure direc-

tion 3 times with identical initial pressure values.

Repairs must only be carried out by the manufacturer.

7.2  Cleaning

WARNING!

Risk of burns

With cleaning there is a risk through hot surfaces.

 

Before cleaning the instrument, allow it to cool sufficiently or use protective 

equipment!

CAUTION!

Physical injuries and damage to property and the environment

Improper cleaning may lead to physical injuries and damage to property and 

the environment. Residual media in the dismounted instrument can result in a 

risk to persons, the environment and equipment.

 

Carry out the cleaning process as described below.

1.  Before cleaning, correctly disconnect the instrument from the pressure supply and 

switch the load circuit off.

2.  Use the requisite protective equipment.

3.  Clean the instrument with a moist cloth.

Electrical connections must not come into contact with moisture!

CAUTION!

Damage to the instrument

Improper cleaning may lead to damage to the instrument!

 

Do not use any aggressive cleaning agents.

 

Do not use any hard or pointed objects for cleaning.

4.  Wash or clean the dismounted instrument, in order to protect persons and the 

environment from exposure to residual media.

8.  Dismounting, return and disposal

WARNING!

Physical injuries and damage to property and the environment through 

residual media

Residual media in the dismounted instrument can result in a risk to persons, 

the environment and equipment.

 

Observe the information in the material safety data sheet for the corresponding 

medium.

 

Wash or clean the dismounted instrument, in order to protect persons and 

the environment from exposure to residual media.

8.1  Dismounting

WARNING!

Risk of burns

During dismounting there is a risk of dangerously hot media escaping.

 

Let the instrument cool down sufficiently before dismounting it!

DANGER!

Danger to life caused by electric current

Upon contact with live parts, there is a direct danger to life.

 

The dismounting of the instrument may only be carried out by skilled personnel.

 

Remove the instrument once the system has been isolated from power sources.

WARNING!

Physical injury

When dismounting, there is a danger from aggressive media and high 

pressures.

 

Observe the information in the material safety data sheet for the corresponding 

medium.

 

Dismount the instrument when there is no pressure.

8.2  Return

Strictly observe the following when shipping the instrument:

All instruments delivered to WIKA must be free from any kind of hazardous substances 

(acids, bases, solutions, etc.) and must therefore be cleaned before being returned.

Содержание PSM-700

Страница 1: ...ty and environmental criteria during production Our management systems are certified to ISO 9001 These operating instructions contain important information on handling the instru ment Working safely requires that all safety instructions and work instructions are observed Observe the relevant local accident prevention regulations and general safety regulations for the instrument s range of use The ...

Страница 2: ... of any damage caused by using the product contrary to its intended use non compliance with these operating instructions assignment of insufficiently qualified skilled personnel or unauthorised modifications to the instrument The general terms and conditions contained in the sales documentation shall apply Subject to technical modifications Further information Internet address www wika de www wika...

Страница 3: ... that lie within its technical performance limits e g max ambient temperature material compatibility For performance limits see chapter 9 Specifications This instrument is not permitted to be used in hazardous areas The instrument has been designed and built solely for the intended use described here and may only be used accordingly The manufacturer shall not be liable for claims of any type based...

Страница 4: ...its original packaging in a location that fulfils the conditions listed above 5 Commissioning operation Before installation commissioning and operation ensure that the appropriate instru ment has been selected in terms of design and specific measuring conditions Tools 6 5 mm socket wrench cross head screwdreiver 20 mm open ended spanner 6 mm Allen key 5 1 Requirements at the measuring point The pr...

Страница 5: ...operty and the environment Should a failure occur aggressive media with extremely high temperature and under high pressure or vacuum may be present at the instrument For these media in addition to all standard regulations the appropriate existing codes or regulations must also be followed 1 Remove 4 screws and open cover 2 Remove the cover s of the electrical connection s 3 Fit suitable cable glan...

Страница 6: ...ch point Carry out switch point setting with matching test assembly see chapter 5 2 Vibrations Decouple the instrument mechanically Short circuit Moisture in the instrument Only use in ambient conditions for which the ingress protection is suitable Contact chatter repeated short duration opening and closing Vibrations Decouple the instrument mechanically 5 5 Setting of the switch differential opti...

Страница 7: ...elow 1 Before cleaning correctly disconnect the instrument from the pressure supply and switch the load circuit off 2 Use the requisite protective equipment 3 Clean the instrument with a moist cloth Electrical connections must not come into contact with moisture CAUTION Damage to the instrument Improper cleaning may lead to damage to the instrument Do not use any aggressive cleaning agents Do not ...

Страница 8: ...s I per IEC 61010 1 2010 case grounded with protective conductor overvoltage category II pollution degree 2 Contact version Switch type Electrical rating AC Electrical rating DC Resistive load Inductive load Resistive load Inductive load 125 V 250 V 125 V 250 V 30 V 125 V 250 V 30 V 125 V 250 V Switch differential Fixed SPDT 10 A 10 A 10 A 10 A 2 A 0 4 A 0 2 A 1 A 0 03 A 0 02 A DPDT 15 A 10 A 10 A...

Отзывы: