Installation and maintenance manual
Ethernet module
DDNN004MHGB/03-2020/Rev.3
7
Step 4:
The left side of the web console contains a tree menu for all settings. The following settings should be
set for correct operation:
Figure 4: Settings
Basic Settings >> Serial Port Settings:
•
… Port Alias
Can be left blank
•
… Baud rate
Should be set to
9600
•
… Data bits
Should be set to
8
•
… Stop bits
Should be set to
1
•
… Parity
Should be set to
None
•
… Flow control
Should be set to
None
or
RTS/CTS
•
… FIFO
Should be set to
Enable.
Press
Submit
to save the settings. Ignore the message that appears and go to the
Operation Modes
:
Basic Settings >> Operation Modes:
•
… Mode
Should be set to
TCP
•
… Role
Should be set to
TCP Server
•
… Local TCP port
Default set to
4001
;
Free to choose
•
… IP address
Default set to
192.168.127.254
;
Free to choose
Press
Submit
again and in the next screen press
Save/Restart
. The red LED on the MiiNePort will
start blinking to indicate that it is restarting.
The settings in step 5 are limited to the absolute minimum needed for correct operation, you are free
to look into the other settings in the web console. It is advisable to add a password to the console via
maintenance >> Change Password
, for increased protection.
Step 5:
If all steps were followed correctly, you should be able to use the module, for instance with UNITOOL.