8

OPERATION

1.

With the 240 VAC power turned on at the circuit
breaker for the furnace, push the air cleaner ON-OFF
switch to the “ON” position (Figure 21).

2.

With the furnace blower running, the air cleaner will
be operating. An arcing or “snapping” sound may be
heard. This will occur occasionally, however the unit
is operating properly.

3.

With the furnace blower running, the Operating Light
should be ON. If the Operating Light is not ON this
signifies that the cells need washing, or that trouble
exists in the unit.

If, after washing the cells, the Operating Light stays off,
the cell could be wet, improperly placed in the cabinet or
may need servicing.

NOTE: An occasional flicker of the light accompanied by
harmless sparking or snapping noise may occur. This is
caused by trapping large particles of dirt. If arcing is
continuous, the cells should be washed or checked for
service problems see Basic SST/UST Service Guide.

Operating
Light

On-Off 
Switch

9.

Remove junction box cover and install the required
bushing into the 3/4 in. Knock out. With the supply
voltage turned off, route three (3) wires into junction
box for connections. (See Fig. 19.)

Insure all wires are clamped, wire connectors prop-
erly installed and grommets used to prevent wire
abrasion.

10. With the cabinet Installed, reinstall pre-filter(s) and

collecting cell(s) (Figure 20).

NOTE: The contact button and handles on the cell
must be facing you and ionizing wires must be on the
air intake side.

11. Install the power pack as follows:

Engage the lip on lower inside edge of power pack in
the flange on cabinet and carefully close the power
pack, making sure that the electrical connector prongs
on the power pack enter the slots in the socket on
cabinet. When the power pack is fully in place, en-
gage the latch and snap it closed.

Front View

Hot

Hot

Grounding
Conductor

Figure 19

Figure 20

Cabinet

Pre-Filters

Handle

Contact
Button

Contact
Button

Collecting Cells

Power Pack

Figure 21

Содержание Electro-Air 10C27S-010

Страница 1: ...Service Guide Technical Repair Guide Repair Parts Part No 37 6123D Replaces 37 6123C 0032 Electronic Air Cleaner Printed In U S A UL Listed CSA Certified by White Rodgers Please read and familiarize y...

Страница 2: ...it must comply with local electric codes or other applicable codes Review and understand local codes prior to in stallation Failure to do so could result in serious personal injury or death CAUTION CA...

Страница 3: ...easy to operate and maintain Its basic components and their functions are as follows See Figure 2 Cabinet mounts to existing duct work and houses the collecting cells and pre filters Collecting Cells...

Страница 4: ...ream from the air filter If your furnace duct system has a pre installed boot discard front cover of boot and slide the air cleaner component inside the boot Applies to 14C27S 010 and 20C27S 010 If fu...

Страница 5: ...t offset to match air filter opening If duct connection to furnace allows less than nine inches for mounting the air cleaner shorten the lateral trunk or attach an offset fitting to the elbow HORIZONT...

Страница 6: ...attached directly Figure 13 or a starting collar can first be fitted to the furnace inlet A butt or slip joint can be used Securely attach the cabinet to furnace inlet using at least two of the mount...

Страница 7: ...t electrical connections to the air cleaner are installed properly see Figure 17 The air cleaner should not have power unless the furnace blower is on Floor Conduit Duct Electronic Air Cleaner Figure...

Страница 8: ...r service problems see Basic SST UST Service Guide Operating Light On Off Switch 9 Remove junction box cover and install the required bushing into the 3 4 in Knock out With the supply voltage turned o...

Страница 9: ...nd rinse thoroughly with clean water 6 Allow cell s and pre filter s to drip dry for a mini mum of 2 hours Cell s and pre filter s may be tipped at a slight angle to expedite the drip dry pro cess 7 R...

Страница 10: ...loose ionizing wire s cracked insulator s etc 3 Collecting cells dirty A Clean cells as instructed in this manual 4 Faulty power supply see power supply checkout procedure BASIC SST UST SERVICE GUIDE...

Страница 11: ...el in locating and correcting any malfunction that might occur to render the air cleaner ineffective or inop erative The air cleaner has been designed with replace able components such as the high vol...

Страница 12: ...tact 4 Using an extension cord apply 240 VAC to power pack Turn power switch to ON position 5 Connect meter negative lead to metal frame of collecting cell Use high voltage probe to measure voltage at...

Страница 13: ...13 NOTES...

Страница 14: ...14 14 REPAIR PARTS...

Страница 15: ...F844 0131 11 Switch F876 0202 F876 0202 F876 0202 F876 0202 12 Power Pack Cabinet Only N A N A N A N A 13 Connector Male F827 0017 F827 0017 F827 0017 F827 0017 14 Power Supply F858 0975 F858 0975 F8...

Страница 16: ...a White Rodgers Electronic Air Cleaner or product containing a White Rodgers Electronic Air Cleaner Although White Rodgers does not extend a warranty directly to consumers White Rodgers does extend a...

Отзывы: