POWER SUPPLY

CHECKOUT PROCEDURE

1.

Turn power switch to the “OFF” position and remove
the power pack from cabinet.

2.

Place power pack on a well insulated workbench.
Connect meter negative (-) lead to the sheet metal
chassis and the high voltage probe to high voltage
contact on back cover of power pack. Connect 240
VAC power to power pack using an extension cord
and turn power switch to the “ON” position. Keep
hands and tools away from high voltage contact.

3.

If Operating Light comes ON and output voltage is
between 6100 and 6800 VDC, power supply is good.

4.

If voltage is good but Operating Light does not come
on, replace Operating Light.

CELL TEST

1.

Place collecting cell on a well insulated workbench
with the cell contact button pointing upward.

2.

Select a power pack (with ozone reduction jumper
intact) that reads between 6100 and 6800 VDC at the
cell contact with no cell attached.

3.

Place power pack on top of  collecting cell ensuring
that there is proper contact between the cell contact
on the power pack contact.

4.

Using an extension cord, apply 240 VAC to power
pack. Turn power switch to “ON” position.

5.

Connect meter negative (-) lead to metal frame of
collecting cell. Use high voltage probe to measure
voltage at collecting cell ionizer or cell plates. Voltage
should be 6100 to 6800 VDC.

NOTE: A new “out-of-box” cell may cause the voltage
to be lower than normal for a short period of time. To
obtain a more accurate measurement, “age” the cell
by applying high voltage to the cell for 15 to 30
minutes.

6

 If voltage is below 6100 VDC, check cell for foreign
objects, bowed/bent/loose plates, broken ionizing
wires or cracked insulators. Wash cells if required. If
Operating Light remains OFF, replace collecting cell.

LINE

WHT/BRN

BLK

W1

E3

E2

Ozone Reduction Jumper

Cut and separate
Ozone Reduction
Jumper

Figure 24

OZONE REDUCTION

All electronic air cleaners typically produce a small amount
of ozone that is within established limits. Some customers
may notice an odor especially at high altitudes or low air
flow rates.

This power supply has a “hairpin” shaped jumper wire
labeled W1 (see Fig 24) that can be cut and separated in
case of such complaints. This will cause the power supply
to limit the maximum operating power to a lower level.

Содержание Electro-Air 10C27S-010

Страница 1: ...Service Guide Technical Repair Guide Repair Parts Part No 37 6123D Replaces 37 6123C 0032 Electronic Air Cleaner Printed In U S A UL Listed CSA Certified by White Rodgers Please read and familiarize y...

Страница 2: ...it must comply with local electric codes or other applicable codes Review and understand local codes prior to in stallation Failure to do so could result in serious personal injury or death CAUTION CA...

Страница 3: ...easy to operate and maintain Its basic components and their functions are as follows See Figure 2 Cabinet mounts to existing duct work and houses the collecting cells and pre filters Collecting Cells...

Страница 4: ...ream from the air filter If your furnace duct system has a pre installed boot discard front cover of boot and slide the air cleaner component inside the boot Applies to 14C27S 010 and 20C27S 010 If fu...

Страница 5: ...t offset to match air filter opening If duct connection to furnace allows less than nine inches for mounting the air cleaner shorten the lateral trunk or attach an offset fitting to the elbow HORIZONT...

Страница 6: ...attached directly Figure 13 or a starting collar can first be fitted to the furnace inlet A butt or slip joint can be used Securely attach the cabinet to furnace inlet using at least two of the mount...

Страница 7: ...t electrical connections to the air cleaner are installed properly see Figure 17 The air cleaner should not have power unless the furnace blower is on Floor Conduit Duct Electronic Air Cleaner Figure...

Страница 8: ...r service problems see Basic SST UST Service Guide Operating Light On Off Switch 9 Remove junction box cover and install the required bushing into the 3 4 in Knock out With the supply voltage turned o...

Страница 9: ...nd rinse thoroughly with clean water 6 Allow cell s and pre filter s to drip dry for a mini mum of 2 hours Cell s and pre filter s may be tipped at a slight angle to expedite the drip dry pro cess 7 R...

Страница 10: ...loose ionizing wire s cracked insulator s etc 3 Collecting cells dirty A Clean cells as instructed in this manual 4 Faulty power supply see power supply checkout procedure BASIC SST UST SERVICE GUIDE...

Страница 11: ...el in locating and correcting any malfunction that might occur to render the air cleaner ineffective or inop erative The air cleaner has been designed with replace able components such as the high vol...

Страница 12: ...tact 4 Using an extension cord apply 240 VAC to power pack Turn power switch to ON position 5 Connect meter negative lead to metal frame of collecting cell Use high voltage probe to measure voltage at...

Страница 13: ...13 NOTES...

Страница 14: ...14 14 REPAIR PARTS...

Страница 15: ...F844 0131 11 Switch F876 0202 F876 0202 F876 0202 F876 0202 12 Power Pack Cabinet Only N A N A N A N A 13 Connector Male F827 0017 F827 0017 F827 0017 F827 0017 14 Power Supply F858 0975 F858 0975 F8...

Страница 16: ...a White Rodgers Electronic Air Cleaner or product containing a White Rodgers Electronic Air Cleaner Although White Rodgers does not extend a warranty directly to consumers White Rodgers does extend a...

Отзывы: