PART 2 : MOTOR INSTALLATION GUIDE

External Solution (Roof Mounted)

Positioning your KLEENAIR Unit:
It is recommended that when the KLEENAIR EXTERNAL UNIT is
ROOF mounted, it is positioned a minimum 2100mm above the
ground surface with a radial clearance of 600mm. Please ensure 
that the KLEENAIR unit is positioned in an environment that is free of 
other gases to enable an efficient expulsion of the cooking bi-products 
and to ensure that back-draft of external gases doesn’t take place.

Please ensure the motor is positioned away from other exhausts
such as re place chimneys, gas fuses, etc. The unit can be mounted
so that it ducts directly through the roof.

STEP 1:

Cut a 200mm diameter hole in the roof to enable the RigidDuct on
the base of the KLEENAIR unit to protrude down into the roof space.
Affix the flashing (optional accessory) to the roof surface. Please
ensure that the hole is cut in a practical position to enable the 
FlexiDuct to be secured.

STEP 2:

Using standard 200mm pipe mounts (optional accessory), mount
the RigidDuct neck to beams, trusses or other appropriate structures
in the roof space. Ensure the RigidDuct protrudes past the top
of the flashing by at least 75mm.

STEP 3:

Remove the mounting bracket from your KLEENAIR unit by rotating
the cover in a anti clockwise direction.

STEP 4:

Fix the mounting bracket to the RigidDuct using the screws
provided.

STEP 5:

Feed power cable through the centre of the mounting bracket and return the KLEENAIR unit on to the mounting bracket and 
fix it by rotating the cover in a clockwise direction. Lock the cover into position by tightening the locking screw.

STEP 6:

Attach the FlexiDuct to the RigidDuct using the pipe clips supplied.

STEP 7:

Attach FlexiDuct from the KLEENAIR unit to the rangehood using pipe clips. Ensure that the duct is pulled tightly to ensure 
that FlexiDuct remains firm and stable during operation. Avoid sharp bends in the duct. 

Gentle bends in the ducting are 

recommended as it assists in muffling noise from the fan unit back to the rangehood.

 If the FlexiDuct needs to be 

extended ,attach the two FlexiDuct ends using a RigidDuct insert, secured by pipe clips or duct tape.

STEP 8:

Attach the male plug of the KLEENAIR unit to the female plug of the rangehood to enable power supply to the fan
motor unit. An extension lead (not supplied) of up to five meters may be added if required.

16

RigidDuct

Outlet

Inlet

Step 7:

Attach FlexiDuct from the KLEENAIR unit to the rangehood using pipe clips. Ensure that the duct is pulled tightly 
to ensure that FlexiDuct remains firm and stable during operation. Avoid sharp bends in the duct. 

Gentle bends in 

the ducting are recommended as it assists in muffling noise from the fan unit back to the rangehood.

  If the 

FlexiDuct needs to be extended attach the two FlexiDuct ends using a RigidDuct insert, secured by pipe clips or 
duct tape.

Step 8:

Attach the male plug of the KLEENAIR unit to the female plug of the rangehood to enable power supply to the fan 
motor unit. An extension lead (not supplied) of up to five meters may be added if required.

Part 2: Motor Installation Guide

External Solution (Roof Mounted)

Positioning your KLEENAIR Unit:
It is recommended that when the KLEENAIR EXTERNAL UNIT is 
ROOF mounted, it is positioned a minimum 2100mm above the 
ground surface with a radial clearance of 600mm. Please ensure that 
the KLEENAIR unit is positioned in an environment that is free of 
other gases to enable an efficient expulsion of the cooking 
bi-products and to ensure that back-draft of external gases doesn’t 
take place. 

Please ensure the motor is positioned away from other exhausts 
such as fire place chimneys, gas flues, etc. The unit can be mounted 
so that it ducts directly through the roof.

Step 1:

Cut a 200mm diameter hole in the roof to enable the RigidDuct on 
the base of the KLEENAIR unit to protrude down into the roof space. 
Affix the dektite (optional accessory) to the roof surface. Please 
ensure that the hole is cut in a practical position to enable the Flexi-
Duct to be secured.

Step 2:

Using standard 200mm pipe mounts (optional accessory), mount 
the RigidDuct neck to beams, trusses or other appropriate struc-
tures in the roof space. Ensure the RigidDuct protrudes past the top 
of the dektite by at least 75mm.

Step 3:

Remove the mounting bracket from your KLEENAIR unit by rotating 
the cover in an anti clockwise direction.

Step 4:

Fix the mounting bracket to the RigidDuct using the screws 
provided.

Step 5:

Feed  power cable through the centre of the mounting bracket and 
return the KLEENAIR unit on to the mounting bracket and fix it by 
rotating the cover in a clockwise direction.  Lock the cover into posi-
tion by tighting the locking screw.

Step 6:

Attach the FlexiDuct to the RigidDuct using the pipe clips supplied.

min 75mm

Mounting Points

Mounting Bracket

Mounting
Bracket

16

RigidDuct

Outlet

Inlet

Step 7:

Attach FlexiDuct from the KLEENAIR unit to the rangehood using pipe clips. Ensure that the duct is pulled tightly 
to ensure that FlexiDuct remains firm and stable during operation. Avoid sharp bends in the duct. 

Gentle bends in 

the ducting are recommended as it assists in muffling noise from the fan unit back to the rangehood.

  If the 

FlexiDuct needs to be extended attach the two FlexiDuct ends using a RigidDuct insert, secured by pipe clips or 
duct tape.

Step 8:

Attach the male plug of the KLEENAIR unit to the female plug of the rangehood to enable power supply to the fan 
motor unit. An extension lead (not supplied) of up to five meters may be added if required.

Part 2: Motor Installation Guide

External Solution (Roof Mounted)

Positioning your KLEENAIR Unit:
It is recommended that when the KLEENAIR EXTERNAL UNIT is 
ROOF mounted, it is positioned a minimum 2100mm above the 
ground surface with a radial clearance of 600mm. Please ensure that 
the KLEENAIR unit is positioned in an environment that is free of 
other gases to enable an efficient expulsion of the cooking 
bi-products and to ensure that back-draft of external gases doesn’t 
take place. 

Please ensure the motor is positioned away from other exhausts 
such as fire place chimneys, gas flues, etc. The unit can be mounted 
so that it ducts directly through the roof.

Step 1:

Cut a 200mm diameter hole in the roof to enable the RigidDuct on 
the base of the KLEENAIR unit to protrude down into the roof space. 
Affix the dektite (optional accessory) to the roof surface. Please 
ensure that the hole is cut in a practical position to enable the Flexi-
Duct to be secured.

Step 2:

Using standard 200mm pipe mounts (optional accessory), mount 
the RigidDuct neck to beams, trusses or other appropriate struc-
tures in the roof space. Ensure the RigidDuct protrudes past the top 
of the dektite by at least 75mm.

Step 3:

Remove the mounting bracket from your KLEENAIR unit by rotating 
the cover in an anti clockwise direction.

Step 4:

Fix the mounting bracket to the RigidDuct using the screws 
provided.

Step 5:

Feed  power cable through the centre of the mounting bracket and 
return the KLEENAIR unit on to the mounting bracket and fix it by 
rotating the cover in a clockwise direction.  Lock the cover into posi-
tion by tighting the locking screw.

Step 6:

Attach the FlexiDuct to the RigidDuct using the pipe clips supplied.

min 75mm

Mounting Points

Mounting Bracket

Mounting
Bracket

16

RigidDuct

Outlet

Inlet

Step 7:

Attach FlexiDuct from the KLEENAIR unit to the rangehood using pipe clips. Ensure that the duct is pulled tightly 
to ensure that FlexiDuct remains firm and stable during operation. Avoid sharp bends in the duct. 

Gentle bends in 

the ducting are recommended as it assists in muffling noise from the fan unit back to the rangehood.

  If the 

FlexiDuct needs to be extended attach the two FlexiDuct ends using a RigidDuct insert, secured by pipe clips or 
duct tape.

Step 8:

Attach the male plug of the KLEENAIR unit to the female plug of the rangehood to enable power supply to the fan 
motor unit. An extension lead (not supplied) of up to five meters may be added if required.

Part 2: Motor Installation Guide

External Solution (Roof Mounted)

Positioning your KLEENAIR Unit:
It is recommended that when the KLEENAIR EXTERNAL UNIT is 
ROOF mounted, it is positioned a minimum 2100mm above the 
ground surface with a radial clearance of 600mm. Please ensure that 
the KLEENAIR unit is positioned in an environment that is free of 
other gases to enable an efficient expulsion of the cooking 
bi-products and to ensure that back-draft of external gases doesn’t 
take place. 

Please ensure the motor is positioned away from other exhausts 
such as fire place chimneys, gas flues, etc. The unit can be mounted 
so that it ducts directly through the roof.

Step 1:

Cut a 200mm diameter hole in the roof to enable the RigidDuct on 
the base of the KLEENAIR unit to protrude down into the roof space. 
Affix the dektite (optional accessory) to the roof surface. Please 
ensure that the hole is cut in a practical position to enable the Flexi-
Duct to be secured.

Step 2:

Using standard 200mm pipe mounts (optional accessory), mount 
the RigidDuct neck to beams, trusses or other appropriate struc-
tures in the roof space. Ensure the RigidDuct protrudes past the top 
of the dektite by at least 75mm.

Step 3:

Remove the mounting bracket from your KLEENAIR unit by rotating 
the cover in an anti clockwise direction.

Step 4:

Fix the mounting bracket to the RigidDuct using the screws 
provided.

Step 5:

Feed  power cable through the centre of the mounting bracket and 
return the KLEENAIR unit on to the mounting bracket and fix it by 
rotating the cover in a clockwise direction.  Lock the cover into posi-
tion by tighting the locking screw.

Step 6:

Attach the FlexiDuct to the RigidDuct using the pipe clips supplied.

min 75mm

Mounting Points

Mounting Bracket

Mounting
Bracket

Содержание A3W12S3

Страница 1: ...PREMIUM QUIET RANGEHOODS OPERATING AND INSTALLATION INSTRUCTIONS FOR WHISPAIR RANGEHOODS ...

Страница 2: ...THE PRODUCT IT IS ESSENTIAL TO READ THESE INSTRUCTIONS PRIOR TO INSTALLATION AND USE IMPORTANT INFORMATION AFTER UNPACKING THE RANGEHOOD PLEASE REVIEW YOUR NEW ITEM TO ENSURE THAT IT HASN T BEEN DAMAGED IN TRANSIT OR IS MISSING ANY COMPONENTS FAILURE TO REPORT ANY ISSUE WITHIN 72 HOURS OF RECEIPT OF YOUR ITEM MAY RESULT IN ADDITIONAL CHARGES ENVIRONMENTAL TIP Information on disposal for users Most...

Страница 3: ...uding control module and lighting 2 Baffle filters 3 Grease trap W5L09S2 W5V09S3 W5V12S3 and A series hoods only 4 Flue cover x2 5 Fixing screws 6 Operating installation guide OPTION 3 ISLAND HUNG CANOPY MODELS INCLUDE W7S09S3 W7V09S3 W7R09S2 AND A7N12S3 INCLUDED IN THE CARTON 1 Main hood housing including control module and lighting 2 Baffle filters 3 Grease trap A series and W7V09S3 hoods only 4...

Страница 4: ...IG 4b MODELS INCLUDE EL 765 EP 1140 and EPP 2010 Unit designed to be mounted externally either on an external wall or penetrating through the roof INCLUDED IN THE CARTON 1 KLEENAIR External Motor Unit 2 Hose Clips x2 3 200mm FlexiDuct 5 Meters Length OPTIONAL ACCESSORIES WHEN ROOF MOUNTING 1 200mm Tile Roof Install Kit HBX200TILE Includes roof flashing for tile roof and mounting brackets x2 2 200m...

Страница 5: ...e Do not flambé under the range hood There must be adequate ventilation of the room of operation when the range hood is used at the same time as appliances burning gas or other fuels In the case of damage to power supply cords use only an authorized service agent or licensed electrician Exhausted air must not be discharged into a chimney or flue This rangehood is a domestic appliance which has bee...

Страница 6: ...ISTS IN MUFFLING NOISE FROM THE EXTERNAL FAN UNIT Ducting Extraction Levels WHISPAIR ducting is designed to ensure optimum performance for your rangehood Please follow the installation instructions carefully Every WHISPAIR rangehood must be ducted to the externally or cavity mounted KLEENAIR unit by the use of non flammable ducting The rangehood must not be ducted into a wall cavity or a ceiling s...

Страница 7: ... noted that the extraction levels are significantly higher Servicing The installation and fitting of the rangehood should be done in such a way that will allow the unit to be removed if service is required Additional costs incurred in the removal such as damage to walls are not covered under warranty It is expected that the stainless steel is cleaned with a quality non abrasive stainless steel cle...

Страница 8: ...this shall be the minimum height for installation Building codes that stipulate a minimum dimension may vary from state to state please check with your local council prior to installation STEP 2 Cut out a central 202mm hole in the shelf for ducting matching the holes position to that of the outlet on top of the hood Additional holes might need to be cut to feed the duct out to the roof cavity STEP...

Страница 9: ...ctricians Standard 10 Amp General Power Outlet GPO required Position GPO as close to the hood unit as possible FASCIA INSTALLING THE GREASE TRAP AND YOUR FILTERS The integrated range of hoods utilise a removable grease trap that is used to catch excess amounts of grease and condensate from the baffle filters This trap can be removed for cleaning The trap consists of a concave channel with fixing p...

Страница 10: ...P09S3 W5H09S3 A5M09S3 A5C09S3 andA5N12S3 Step 1 Measure the height of the hood from the base to the top of the mounting hooks NOTE The height of the underside of the hood body must be a minimum of 600mm above an electric cooktop 650mm above a gas cook top and a maximum height of 1200mm If the instructions of the hob specify a greater distance than the minimum detailed this shall be the minimum hei...

Страница 11: ...d secure to the chimney bracket You may need to drill some new holes through the cover and bracket to secure the chimney cover STEP 11 Attach the male plug of the rangehood unit to mains power supply Note to Electricians Standard 10 Amp General Power Outlet GPO required Position GPO as close to the hood unit as possible ...

Страница 12: ...upporting beams on the ceiling STEP 3 Adjust and fix the roof bracket to the desired length STEP 4 Secure the FlexiDuct down the inside of the roof bracket taking care not to constrict the duct STEP 5 Slide the stainless steel chimney covers up and secure to the bracket You may need to drill some new holes through the cover and bracket to secure the chimney cover depending on desired length In ord...

Страница 13: ... INSTALLATION GUIDE STEP 7 Attach the male plug of the rangehood unit to mains power supply Note to electricians Standard 10 Amp General Power Outlet GPO required Position GPO as close to the hood unit as possible ...

Страница 14: ... 200mm Ducting Attached to Internal Hood Unit Outlet Ducting Pulled Tight Gentle Bend In Ducting Maintain 200mm Duct Diameter EXTERNAL KLEENAIR MOTOR SOLUTION Roof Mounted Roof INLINE KLEENAIR MOTOR SOLUTION Wall Vented Wall Fan Power Supply Attached to Internal Hood Unit 200mm Ducting Attached to Internal Hood Unit Outlet Gentle Bend In Ducting Maintain 200mm Duct Diameter Ducting Pulled Tight IN...

Страница 15: ... away from other exhausts such as fire place chimneys gas flues etc The inline unit an be mounted so that it ducts directly through the wall or eave Step 1 Establish a suitable position in the roof or wall cavity for the KLEENAIR unit ensuring that the distance between the KLEENAIR unit and the outside vent is under 800mm The KLEENAIR unit must be located a minimum of 3 metres from the hood unit S...

Страница 16: ... hole in the wall to enable the rigid duct on the back of the KLEENAIR unit to protrude Please ensure that the hole is cut in a practical position to enable the FlexiDuct to be secured Step 2 Remove the mounting bracket from your KLEENAIR unit by twisting the cover in an anti clockwise direction Mark at least four mounting points on the wall and pre drill the holes required Step 3 Attach the Flexi...

Страница 17: ...in 75mm Mounting Points Mounting Bracket Mounting Bracket 16 RigidDuct Outlet Inlet Step 7 Attach FlexiDuct from the KLEENAIR unit to the rangehood using pipe clips Ensure that the duct is pulled tightly to ensure that FlexiDuct remains firm and stable during operation Avoid sharp bends in the duct Gentle bends in the ducting are recommended as it assists in muffling noise from the fan unit back t...

Страница 18: ... to adjust the minute Time will be automatically saved as default if not adjusted after 5 seconds Operation Operating your control panel with the 4 Button Control Turning the extraction function ON or OFF In standby mode press button 1 to turn on operating mode then press button 1 or 2 to change the speed The hood has three speed options and a boost speed plus the off function To turn hood off pre...

Страница 19: ... the 1st velocity and illuminate the respec tive LED The function will switch on when the Key is released When the LED is switched off and another velocity is activated pressing the Key will imply selection of the 1st velocity switching on of the respective LED and switching off of the LED associated with the velocity that was previously selected When the LED is on pressingthe Key will imply the s...

Страница 20: ...imer function activated will deactivate it 1 1st Velocity When the LED is switched off non prolonged pressing of the key will switch on the hood at the 1st velocity and illuminate the respec tive LED The function will switch on when the Key is released When the LED is switched off and another velocity is activated pressing the Key will imply selection of the 1st velocity switching on of the respec...

Страница 21: ... the product returns to the manufacturer s intended operating condition CLEANING THE BAFFLE FILTERS The baffle filters and grease trap can be removed by sliding them from their mounted position within the hood and washed in the dishwasher or by hand Use hot water and liquid detergent After cleaning leave the filters and trap to dry before placing back in the hood CHANGING THE LAMP WARNING Please b...

Страница 22: ... 0 3 9700 9100 or in New Zealand call 64 0 9 964 0400 to speak with our friendly customer service consultants We suggest you have the following information close at hand to make the process as easy as possible 1 Model number of your rangehood 2 A copy of your WHISPAIR proforma invoice 3 Address details of where the appliance has been installed Any associated or ancillary costs to be incurred by yo...

Страница 23: ...NOTES ...

Страница 24: ...Bangholme Road Dandenong South Victoria Australia 3175 Australian Sales Service T 61 03 9700 9100 E info whispair com au www whispair com au New Zealand Sales Service T 64 9964 0400 E info whispair co nz www whispair co nz PREMIUM QUIET RANGEHOODS ...

Отзывы: