TECH SHEET - DO NOT DISCARD
PAGE 3
FOR SERVICE TECHNICIAN’S USE ONLY
PART NO. W10054150
DISPLAY
DESCRIPTION
EXPLANATION / RECOMMENDED PROCEDURE
PF
Power
Failure
PF
flashes to indicate that a power failure
occurred while the dryer was running. Press
START to continue the cycle, or press
Pause/Cancel to clear the display.
AF
Restricted
Airflow
Condition
AF
flashes if a restricted airflow condition exists.
Check to make sure the lint screen is clean, the
door seal is in place and the vent is not
obstructed.
F-0
1
Primary
Control
Failure
F-01
flashes when there is a primary control
failure. Replace the machine control electronics.
See Accessing & Removing the Electronic
Assemblies, page 11.
F-02
Keypad/
User Interface
Failure
F-02
flashes when there is a stuck button or user
interface mismatch. This fault code will ONLY
appear when in the diagnostic test mode. See
TEST #6, page 10.
F-22
Exhaust
Thermistor
Open
F-22
flashes if the exhaust thermistor is open.
See TEST #4a, page 8.
F-23
Exhaust
Thermistor
Shorted
F-23
flashes if the exhaust thermistor has
shorted. See TEST #4a, page 8.
F-24
Inlet
Thermistor
Open
F-24
flashes if the inlet thermistor is open.
This fault code will ONLY appear when in the
diagnostic test mode. See TEST #4a, page 8.
F-25
Inlet
Thermistor
Shorted
F-25
flashes if the inlet thermistor is shorted.
This fault code will ONLY appear when in the
diagnostic test mode. See TEST #4a, page 8.
F-26
Motor Drive
System Failure
F-26
flashes if there is a motor drive system
failure. See TEST #3, page 7.
F-28
Moisture
Sensor Open
F-28
flashes if the moisture sensor strip is open.
This fault code will ONLY appear when in the
diagnostic test mode. See TEST #5, page 9.
F-29
Moisture
Sensor
Shorted
F-29
flashes if the moisture sensor strip has
shorted. This fault code will ONLY appear when in
the diagnostic test mode. See TEST #5, page 9.
F-30
Restricted
Airflow
Condition
F-30
flashes if a restricted airflow condition
exists. This fault code will ONLY appear when in
the diagnostic test mode. Check to make sure the
lint screen is clean, the door seal is in place and
the vent is not obstructed.
DISPLAY FAULT CODES
The fault codes below would be indicated when attempting to start a
drying cycle or after activating the diagnostic test mode.
PROBLEM
POSSIBLE CAUSE / TEST
NOTE:
Possible Cause/Tests MUST be performed
in the sequence shown for each problem.
WON’T POWER UP.
(No response when
buttons are pressed.)
1. Supply connections. See TEST #1, page 6.
2. Check harness connections.
3. User interface assembly. See TEST #6, page 10.
WON’T START CYCLE
WHEN START BUTTON
IS PRESSED.
1. If number display flashes, check to be sure the
door is completely shut, and press and hold down
START for about 1 second.
2. See TEST #3, page 7.
3. See TEST #7, page 10.
WON’T SHUT OFF
WHEN EXPECTED.
1. Check Pause/Cancel button. See TEST #6,
page 10.
2. User interface assembly. See TEST #6, page 10.
3. Moisture sensor. See TEST #5, page 9.
CONTROL WON’T
ACCEPT SELECTIONS.
User interface assembly. See TEST #6, page 10.
WON’T HEAT.
1. Heater. See TEST #4, page 8.
2. Check harness connections.
3. Check installation.
HEATS IN AIR CYCLE.
Heater. See TEST #4, page 8.
SHUTS OFF BEFORE
CLOTHES ARE DRY.
1. Check the dryness setting for auto cycles.
2. Check for full lint screen.
3. Check for clogged vent.
4. Moisture sensor. See TEST #5, page 9.
5. Dryness adjust. See Adjusting Customer-Focused
Drying Modes, page 10.
TROUBLESHOOTING GUIDE
Some tests will require accessing components. See figure 2, page 6 for
component locations.
Red
Blue Blue-White
Green-Yellow
Red
Black-White
PLUGGABLE DRIVE MOTOR SWITCH
1M 2M 3M 5M 6M
=
Contacts closed
Contacts
Function
Start
Run
CENTRIFUGAL SWITCH (MOTOR)
Now press any key (except Pause/Cancel) and the control will
advance through each step of the following sequence:
SINGLE ELEMENT MODELS:
2. Motor + heater.
➔
Flash “Casual” LED.
3. No loads on (motor + heater off).
➔
Flash “Normal” LED.
4. Repeat using same button.
➔
Start sequence again at 1.
DUAL ELEMENT MODELS:
2. Motor + heater 1.
➔
Flash “Casual” LED.
3. Motor + heater 2.
➔
Flash “Timed Dry” LED.
4. Motor + heater 1 + heater 2 + drum light.
➔
Flash “Drum Light” LED.
5. No loads on (motor + heaters off).
➔
Flash “Normal” LED.
6. Repeat using same button.
➔
Start sequence again at 1.
DEACTIVATING THE MANUAL LOAD TEST
Press the Pause/Cancel button to exit this mode.