background image

Plan installation to use the fewest number of elbows and turns.

Allow as much room as possible when using elbows or making
turns. Bend vent gradually to avoid kinking.

Vent outlet is located at the center of the bottom dryer back.

The vent can be routed up, down, left, right, behind the dryer, or
straight out the back of the dryer.

Vent System Length

Maximum length of vent system depends upon the type of vent
used, number of elbows and type of exhaust hood. The maximum
length for rigid metal venting is shown in the chart.

For vent systems not covered by the vent specification chart, see
Whirlpool Service Manual, “Exhausting Whirlpool Dryers,” Part
No. LIT603197, available from your Whirlpool parts distributor.

If dryer is installed in a confined area, such as a bedroom,
bathroom or closet, provision must be made for enough air
for combustion and ventilation. (Check governing codes and
ordinances.) See “Recessed Area and Closet Installation
Instructions” in the “Location Requirements” section.

A four-inch outlet hood is preferred. However, a 2

1

/

2

" (640 mm)

outlet exhaust hood may be used. A 2

1

/

2

" (640 mm) outlet creates

greater back pressure than other hood types. For permanent
installation, a stationary vent system is required.

8

ordinances or refer to the “Recessed Area and Closet Installation
Instructions” in the “Location Requirements” section.

Gas Supply Pressure Testing

A

1/8

" NPT minimum plugged tapping, accessible for gauge

testing, must be installed immediately upstream of the gas supply
connection to the dryer.

The dryer must be disconnected from the gas supply piping
system during any pressure testing of the system at test
pressures in excess of

1/2

" psig.

Venting Requirements

WARNING:

To reduce the risk of fire, this dryer MUST BE

EXHAUSTED OUTDOORS.

IMPORTANT:

Observe all governing codes and ordinances.

Only rigid or flexible metal duct shall be used for exhausting.

The dryer vent must not be connected into any gas vent,
chimney, wall, ceiling, attic, crawlspace, or a concealed
space of a building.

Do not use an exhaust hood with a magnetic latch.

Do not install flexible metal vent in enclosed walls, ceilings,
or floors.

4" (102 mm) heavy metal vent and clamps must be used.

Use clamps to seal all joints. Vent must not be connected or
secured with screws or other fastening devices which extend
into the interior of the vent and catch lint. Do not use duct tape.

Use a heavy metal vent. Do not use plastic or metal foil vent.

Rigid metal vent is recommended to prevent crushing and kinking.

Flexible metal vent must be fully extended and supported when
the dryer is in its final position. Remove excess flexible metal vent
to avoid sagging and kinking that may result in reduced airflow
and poor performance.

The total length of flexible metal duct shall not exceed 7

3

/

4

ft (2.4 m).

An exhaust hood should cap the vent to prevent rodents and
insects from entering the home or business.

Exhaust hood must be at least 12" (305 mm) from the ground or
any object that may be in the path of the exhaust (such as
flowers, rocks, or bushes).

If using an existing vent system, clean lint from the entire length
of the system and make sure exhaust hood is not plugged with
lint. Replace any plastic or metal foil vent with rigid metal or
flexible metal vent.

WARNING

Fire Hazard

Use a heavy metal vent.

Do not use a plastic vent.

Do not use a metal foil vent.

Failure to follow these instructions can result in death
or fire.

A

B

Exhaust Air Flow
A. Better
B. Good

Rigid Metal Vent

No. of 90° turns

4" (102 mm) Diameter Exhaust Hoods

Maximum Vent Length

64 ft. (19.5 m)
54 ft. (16.5 m)
44 ft. (13.4 m)
35 ft. (10.7 m)
27 ft. (8.2 m)

0
1
2
3
4

58 ft. (17.7 m)
48 ft. (14.6 m)
38 ft. (11.6 m)
29 ft. (8.8 m)
21 ft. (6.4 m)

Box Hood and Louvered Style

Angled Hood Style

Содержание CEM2940TQ

Страница 1: ...INSTALLATION INSTRUCTIONS COMMERCIAL DRYER Gas 120 Volt 60 Hz or Electric 120 240 Volt 60 Hz Table of Contents 2 8563800B www roper com ...

Страница 2: ... WARNING DRYER SAFETY 2 INSTALLATION REQUIREMENTS 4 Tools and Parts 4 Location Requirements 5 Electrical Requirements 6 Gas Supply Requirements 7 Venting Requirements 8 INSTALLATION INSTRUCTIONS GAS DRYER 10 Install Coin Slide and Coin Box 10 Make Gas Connection 10 FOR YOUR SAFETY Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance It i...

Страница 3: ...bor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier Clear the room building or area of all occupants IMPORTANT The gas installation must conform with local codes or in the absence of local codes with the National Fuel Gas Code ANSI Z22...

Страница 4: ...oors with equivalent air openings are acceptable The dryer must be exhausted outdoors No other fuel burning appliance may be installed in the same closet as the dryer INSTALLATION REQUIREMENTS Tools and Parts Gather the required tools and parts before starting installation Read and follow the instructions provided with any tools listed here Tools needed WARNING Explosion Hazard Keep flammable mate...

Страница 5: ...EXHAUST 4 3 4 121 mm 13 330 mm 1 1 4 32 mm BACK VIEW 4 102 mm dia 1 25 mm non coin operated models 7 1 8 181 mm coin operated models 7 7 8 200 mm SIDE VIEW 35 889 mm 25 1 2 648 mm 27 686 mm 37 940 mm 14 356 mm ELECTRIC GAS EXHAUST LEFT OR RIGHT SIDE EXHAUST 4 3 4 121 mm 13 330 mm 1 1 4 32 mm BACK VIEW 4 1 4 108 mm 6 3 4 152 mm 4 102 mm dia 1 25 mm non coin operated models 7 1 8 181 mm coin operate...

Страница 6: ...ical installer to ensure that the electrical installation is adequate and in conformance with the National Electrical Code ANSI NFPA 70 latest edition and all local codes and ordinances GROUNDING INSTRUCTIONS SAVE THESE INSTRUCTIONS For a grounded cord connected dryer This dryer must be grounded In the event of a malfunction or breakdown grounding will reduce the risk of electric shock by providin...

Страница 7: ... MA 02269 The design of this dryer has been certified by CSA International for use at altitudes up to 10 000 feet 3048 m above sea level at the B T U rating indicated on the model serial plate Burner input adjustments are not required when the dryer is operated up to this elevation When installed above 10 000 feet 3048 m a four percent 4 reduction of the burner B T U rating shown on the model seri...

Страница 8: ...IMPORTANT Observe all governing codes and ordinances Only rigid or flexible metal duct shall be used for exhausting The dryer vent must not be connected into any gas vent chimney wall ceiling attic crawlspace or a concealed space of a building Do not use an exhaust hood with a magnetic latch Do not install flexible metal vent in enclosed walls ceilings or floors 4 102 mm heavy metal vent and clamp...

Страница 9: ...oom Back draft Damper Kits Part No 3391910 are available from your Whirlpool dealer and should be installed in each dryer s vent to prevent exhausted air from returning into the dryers and to keep the exhaust in balance within the main vent Unobstructed air openings are required Each vent should enter the main vent at an angle pointing in the direction of the airflow Vents entering from the opposi...

Страница 10: ...vice door Put the coin vault with lock and key in the meter case opening 8 Remove cardboard or hardboard from under dryer WARNING Excessive Weight Hazard Use two or more people to move and install dryer Failure to do so can result in back or other injury Make Gas Connection 1 Remove red cap from gas pipe 2 Connect gas supply to dryer Use pipe joint compound resistant to the action of L P gas for g...

Страница 11: ... door of the meter case by lifting it up at the back Install the money accepting device Refer to manufacturer s instructions for proper installation WARNING Excessive Weight Hazard Use two or more people to move and install dryer Failure to do so can result in back or other injury For dryers using coin slides use adapter kit supplied with dryer 7 Replace the meter case service door Put the coin va...

Страница 12: ...the power supply cord to the external ground conductor screw Tighten screw 8 Connect the neutral wire white or center of the power supply cord under the center screw of the terminal block Tighten screw 9 Connect the other wires to outer terminal block screws Tighten screws 10 Tighten strain relief screws 11 Insert tab of the terminal block cover into slot of the dryer rear panel Secure cover with ...

Страница 13: ...ter terminal block screws Tighten screws 8 Tighten strain relief screws 9 Insert tab of the terminal block cover into slot of the dryer rear panel Secure cover with hold down screw D A C B 5 Remove the center terminal block screw 6 Remove the appliance neutral ground wire from the external ground conductor screw Connect the appliance neutral ground wire and the neutral wire white or center of the ...

Страница 14: ... bare ground wire at 5 127 mm Cut 11 2 38 mm from 3 remaining wires Strip insulation back 1 25 mm Shape ends of wires into a hook C B A E D F 5 Remove the center terminal block screw 6 Remove the appliance neutral ground wire from the external ground conductor screw Fasten under center silver colored terminal block screw 7 Connect the ground wire green or bare of the direct wire cable to the exter...

Страница 15: ... wire cut green or bare wire even with outer covering Three wire with ground wire green or bare wire cut short Wire is not used Dryer is grounded through neutral conductor to disconnect box 1 25 mm of wires stripped of insulation 3 1 2 89 mm 5 Loosen or remove the center terminal block screw 6 Place the hooked end of the neutral wire white or center of the direct wire cable under the center screw ...

Страница 16: ...eek Just dial 1 800 NO BELTS 1 800 662 3587 the call is toll free When you call you will need the dryer model number and serial number Both numbers can be found on the serial rating plate located in the dryer door well You can install the 30 minute or 60 minute timing cam shipped with dryer as follows 1 Unplug dryer or disconnect power 2 Unlock meter case 3 Turn the timing cam by hand until the V ...

Отзывы: