Set switches and jumpers on the SP40/2 as follows:
•
Set jumper J2 to 1V position.
•
Set SW4 to the contact closure (CC) position.
•
Remove jumper W5 to enable supervision of the CC input wiring.
Set switches and jumpers on the SP4-RMX as follows
•
Set SW1 to the SP40 position.
•
Set Jumper J1 to 1V.
•
Set switches on switch block SW3 to the ON position for each SPRM connected. Insure the corresponding switch is OFF for any
SPRM inputs not used.
•
Set S1 switch on SW2 to the desired position according to Table 1. Set S2 to ON. Switch S3 to the ON Position.
SP40/2 with Two Ganged SP4-RMX Modules
10K
EOLR
AUX IN
CC/NAC
SP40/2
24 VDC
10K
EOLR
10K
EOLR
10K
EOLR
10K
EOLR
S3
S2
S3
SW
2
RM3
V
O
L
RM2
V
O
L
RM
1 V
O
L
1V
25V
70
V
AU
X
VOL
R3
7
J1
S3
S2
S1
SW2
RM3
V
O
L
RM2
V
O
L
RM1
V
O
L
1V
25V
70V
AU
X V
O
L
R3
7
J1
Figure 4:
Two Ganged SP4-RMS Modules
Set switches and jumpers on the SP40/2 as follows:
•
Set jumper J2 to 1V position.
•
Set SW4 to the contact closure (CC) position.
•
Remove jumper W5 to enable supervision of the CC input wiring.
Set switches and jumpers on the SP4-RMX as follows
•
Set SW1 to the SP40 position.
•
Set Jumper J1 to 1V.
•
Set switches on switch block SW3 to the ON position for each SPRM connected. Insure the corresponding switch is OFF for any
SPRM inputs not used.
•
Set switch S1 on SW2 to the desired position according to Table 1. Set S2 to ON. Switch S3 to the OFF position.