Wheelock SP4-RMX Скачать руководство пользователя страница 10

 

 

     P84557 

 

 

          Sheet 10 of 14 

 
 
Configuration: 
 

The following table describes the switch and jumper settings on the SP4-RMX 
 
 

Table 1: 

Switch and Jumper Descriptions 

 

Switches Remarks 

SW1 – SP40/SPB Select 

Selects SP40 or SPB use 

SW2  

   S1 - Priority 

ON – Sets priority order of RM1, RM2, RM3. 
OFF – Sets remote microphones for first in use, first out. 

   S2 – Not Used 

For future use. Leave in ON position. 

   S3 – Gang Mode 

OFF – Gang mode. Both SP4-RMX modules set to OFF. 
ON – Single SP4-RMX module. 

SW3 – RM Input Select 

ON – Selects Corresponding RM input. 
OFF – proper position when RM input not used. 

Jumper Remarks 

J1 – AUX Input Voltage 
Select 

 

   1V 

Set for SP40/2. 

   25V/70V 

Set for audio output of SP40/2 during SPB mode. 

 
 

Operation: 

 
 
The SP4-RMX is capable of expanding the remote microphone capabilities of the SP40/2 and SPB audio boosters.  In SP40 mode, 
each SP4-RMX provides the capability of connecting and supervising up to three SPRM emergency remote microphone modules.  In 
SPB mode, the SPRM-GP (General Page Remote Microphones) must be used.  These microphones are for general pages only.  These 
pages are non-emergency messages.  Any trouble condition on the SPRM modules, input and output wiring will light the system 
trouble LED indicator and one of the trouble location LED indicators.  Follow the trouble shooting procedures if these LED indicators 
are lit.  

 
 

When the SP4-RMX is used to expand the remote microphone modules for the SP40/2, it is connected to the AUX IN on the SP40/2. 
The priority selection of the remote microphone modules will be after the SP40/2 onboard microphone (Priority 1). The priorities of 
the SPRM modules of a second SP4-RMX gang connected to the first will follow the priorities of the SPRM modules connected to the 
first SP4-RMX. 
 
 

Содержание SP4-RMX

Страница 1: ...e number of optional Remote Microphones SPRM or SPRM GP to three The PCB assembly is mounted in an enclosure READ THESE INSTRUCTIONS CAREFULLY BEFORE USING THIS PRODUCT NOTE All CAUTIONS and WARNINGS...

Страница 2: ...out basis Technical Specifications Electrical Input Voltage 24 VDC Input Current 52mA max RM Page 62mA max Standby Auxiliary Audio Input 1Vrms Relay Ratings K1 and K3 2A 30Vdc 1pF K2 K4 K5 and K6 1A...

Страница 3: ...o all qualified personnel who operate test maintain or service SAFEPATH4 products 2 Carefully unpack the SP4 RMX and make sure each item described on the packing slip is present and undamaged 3 Mount...

Страница 4: ...MX Cable Size 14 22 AWG Shielded One end of the shield must be connected at the SafePath4 panel or SP4 RMX enclosure Maximum Length 20 Feet Restrictions All wiring between SP40 2 or Audio Booster and...

Страница 5: ...P84557 D Sheet 5 of 14 6 00 CONDUITKNOCKOUTS 2 PLACES BOTHENDS 11 00 MOUNTINGHOLES MOUNTINGHOLES GROUND TERMINALS Figure 2 SP4 RMX Mounting NOTE Drawing is not to scale...

Страница 6: ...J1 ALL CONNECTIONS BETWEEN SP40 AND RMX ARE SUPERVISED THESE CONNECTIONS MUST BE RUN IN NO MORE THAN 20 FT OF CONDUIT AND WITHIN THE SAME ROOM ALL CONNECTIONS BETWEEN RMX AND REMOTE MICS ARE SUPERVIS...

Страница 7: ...RMX Modules 10K EOLR AUX IN CC NAC SP40 2 24 VDC 10K EOLR 10K EOLR 10K EOLR 10K EOLR S3 S2 S3 SW2 RM3 VOL RM2 VOL RM1 VOL 1V 25V 70V AUX VOL R37 J1 S3 S2 S1 SW2 RM3 VOL RM2 VOL RM1 VOL 1V 25V 70V AUX...

Страница 8: ...HESE CONNECTIONS MUST BE RUN IN NO MORE THAN 20FT OF CONDUIT AND WITHIN THE SAME ROOM REFER TO FIGURE 3 FOR SPRM G P CONNEC TIONS ALL CONNEC TIONS ARE SUPERV ISED SP40 2 SP4 RMX SPB 10K OHM EOLR 10K O...

Страница 9: ...SPRM connected Insure the corresponding switch is OFF for any SPRM inputs not used Set switch S1 on SW2 to the desired position according to Table 1 Set S2 to ON Switch S3 to the ON position Set switc...

Страница 10: ...of the SP40 2 and SPB audio boosters In SP40 mode each SP4 RMX provides the capability of connecting and supervising up to three SPRM emergency remote microphone modules In SPB mode the SPRM GP Gener...

Страница 11: ...o booster modules the SP40 2 AUDIO OUT is connected to the SP4 RMX AUX IN and the SP4 RMX AUDIO OUT is connected to the SPB AUDIO IN This means that the priority level of the SPRM GP modules are after...

Страница 12: ...Use the following troubleshooting table to locate the trouble area Table 4 Trouble LED Indicators D30 SYS PWR D29 SYS TRB LED Indicator Remarks ON OFF Normal OFF OFF 24VDC not applied Check PWR IN ter...

Страница 13: ...13 of 14 S3 S2 S1 SW2 RM3 VOL RM2 VOL RM1 VOL 1V 25V 70V AUX VOL R37 J1 AUX TRB ALM TRB RM1 TRB WIRE SHT WIRE OPEN SYS TRB SYS PWR D24 D25 D26 D27 D28 D23 D22 D29 D30 RM2 TRB RM3 TRB Figure 6 SP4 RMX...

Страница 14: ...SPECIFICATION ABUSE ACCIDENT OR OTHER OPERATING CONDITIONS BEYOND WHEELOCK S CONTROL SOME WHEELOCK PRODUCTS CONTAIN SOFTWARE WITH RESPECT TO THOSE PRODUCTS WHEELOCK DOES NOT WARRANTY THAT THE OPERATI...

Отзывы: