Two SP4-RMX modules can be ganged together when connecting them to an SP40/2 panel. This provides a maximum of six remote
microphones providing “All Call” for the entire system. One SP4-RMX can be connected to each audio booster providing three non-
alarm/general page remote microphones for that audio booster audio output. Each SP4-RMX provides a line level, 600 Ohm auxiliary
audio input.
There are two configurations for the Priority levels of the remote microphones can be set. One configuration sets the priorities as:
RM1, priority 1; RM2, priority 2; and RM3, priority 3. For instance, if RM3 is broadcasting, RM1 or RM2 can override RM3. The
other configuration allows the first remote microphone to broadcast to have the top priority until it completes its message. The remote
microphones operate on a first in – first out basis.
Technical Specifications:
Electrical
Input
Voltage
24
VDC
Input
Current 52mA
max RM
Page
62mA
max
Standby
Auxiliary Audio Input 1Vrms
Relay Ratings
K1 and K3: 2A, 30Vdc, 1pF
K2, K4, K5, and K6: 1A, 30Vdc, 1pF
Remote Microphone
(SPRM)
Mechanical
Dimensions (H x W x D) 13.0" x 7.6" x 2.15", 33cm x 19.4cm x 5.4cm
Weight
3.8
pounds,
1.7kg
Enclosure
0.050"
Steel
Finish
Black
Mounting Indoor
Surface
Mount
Top
and
Bottom
Wiring
Entry
Environmental
(Meets UL requirements)
Operating Temperature 32° to 120.2
° F (0° to +49° C)
Storage Temperature -4° to 158° F (-20° to 70° C)
Humidity 85±5%
@
30±2°
C
Non-condensing
Installation:
The lives of people depend upon your safe installation of the SP4-RMX. Please read, understand and follow the specific
installation instructions set forth below to avoid damage to the SP4-RMX and equipment connected to it. Installation should be
conducted only by qualified persons in accordance with procedures in this manual.
WARNING: SHUT OFF ALL POWER BEFORE STARTING THE INSTALLATION. ELECTRICAL SHOCK CAN