background image

 

6

Maintenance/Repair Introduction 

 

By nature, heating, ventilation and air conditioning equipment deteriorates with normal use.  To 
help alleviate this, preventive maintenance is required.  When properly maintained, the systems 
will experience improved efficiency and increased equipment life.

 

 
Failure to perform preventive maintenance of The Whalen Company equipment, by a licensed 
HVAC technician per the recommended schedule, will result in loss of factory warranty.  Logs 
are provided in this manual and are to be filled out documenting all repairs and maintenance 
performed.  

 

Preventive Maintenance 

 

 

General  (Annually) 

o

  Visual Inspection for corrosion and proper mounting, alignment and sealing 

  Installation of unit 

  Air Connections 

  Water connections 

  Condensate drainage pitch 

o

  Functional Inspection of operation 

  Heating mode 

  Cooling mode 

  Amperage draw 

  Supply voltage 

 

 

Coils  (Annually) 

o

  Clean the coils by removing the blower panel and brushing the fins with a stiff, plastic 

bristle brush, taking care not to bend or damage the fin surface.  After brushing, the 
coil should be vacuumed to remove loose dirt. 

o

  Check insulation for proper coverage to maintain efficiency and prevent sweating. 

o

  Piping – inspect all connections for leaks and corrosion. 

o

  Valves – Check for proper operation, corrosion and leaking. 

 

 

Motor  (Annually) 

o

 

If there are no oil tubes present, the motor is permanently lubricated. 

o

  If oil tubes are provided on the motor, lubricate every six months with SAE-10 weight, 

non-detergent oil.  Inspect the motor and blower assembly every time the motors are 
oiled for excessive accumulation of dust and dirt.  If necessary, remove the blower 
and vacuum. If this situation does occur, increase routine filter maintenance. 

“DO 

NOT OVER OIL”

 

o

  Check amperage draw against the nameplate information 

o

  Check bearings for wear and noise. 

o

  Wheel – Check for free spinning movement 

o

  Check for tightness of set screws. 

o

  Check blades for damages. 

 

 

Drain Pan  (Annually)

 

o

  The drain pan must be inspected before summer operation.  All debris in the drain 

pan should be removed so the condensate will flow out easily.  Periodic inspection of 
the drain pan and condensate piping should be performed during the summer 

Содержание VW series

Страница 1: ...Installation Operating Maintenance Instructions Vertical Models VW ...

Страница 2: ... Team about any problems or conditions that you do not understand Safety Symbols and Labels used in these instructions Receiving Upon delivery examine each unit carefully for shipping damage Immediately report any freight damage to the freight carrier and file a freight claim with the carrier All units are shipped FOB factory therefore The Whalen Company is not responsible for damage during transi...

Страница 3: ...the building drain The Whalen Company will not assume any liability for damage caused as a result of the condensate drain line not being properly pitched or trapped The use of a secondary drain pan under the entire unit with a separate drain line is advised in areas where water damage is very critical See the Fan Coil Piping Instructions on Page 5 CAUTION It is the sole responsibility of the custo...

Страница 4: ... the Valve Stem Marking as shown If not pivot the gray Release Lever and while pivoted turn the large black lever accordingly 3 Set both dip switches in the position toward the black lever 4 Place the green actuator assembly onto the valve and re insert the pins Fan Coil Piping Instructions CHILLED AND HOT WATER COILS Purpose This data is intended to explain piping arrangements for chilled and hot...

Страница 5: ...e chilled water coil is operating or the hot water coil is operating but not both at the same time When the conditioned space thermostat is satisfied both the chilled and hot water control valves are deactivated The same rule applies for inlet and outlet locations as explained above in Two Pipe Coils See diagram 2 Each chilled and hot water coil is controlled individually so a pipe sensor is not r...

Страница 6: ...e not to bend or damage the fin surface After brushing the coil should be vacuumed to remove loose dirt o Check insulation for proper coverage to maintain efficiency and prevent sweating o Piping inspect all connections for leaks and corrosion o Valves Check for proper operation corrosion and leaking Motor Annually o If there are no oil tubes present the motor is permanently lubricated o If oil tu...

Страница 7: ...r and recorded on the Filter Replacement Log Once before the heating season and once before the cooling season Periodic checks should be made during the cooling season to insure that excessive dust or lint is not accumulating to the extent of interrupting free air flow If excessive dirt accumulates the filter should be changed more frequently o Reusable Cleanable Filters should be thoroughly clean...

Страница 8: ...8 Maintenance Repair Log Address Unit No Model Description Model No Serial No Voltage Amps Start Up Date Date Descriptionof Service Parts Required Signature ...

Страница 9: ...9 Filter Replacement Log Address Unit No Model Description Model No Serial No Replacement Date Signature Replacement Date Signature Replacement Date Signature ...

Страница 10: ...upply Voltage 17 Proper Steam Supply Pressure To Unit 15 PSI Max 45 Record Ambient Temperatures 18 All Services To Unit In Code Compliance 46 Check All Wiring For Secure Connections 19 All Shipping Screws Brace Removed 47 Close All Unit Isolation Valves 20 Unit Protected From Dirt Foreign Matter 48 Flush Water Systems 21 Filter Is Clean Free Of Construction Debris 49 Fill Systems With Water Refrig...

Отзывы: