background image

 

5

The inlet is always at the bottom of the coil and the outlet is always at the top of the coil.  All 
coils are piped so that the inlet is always on the row farthest downstream from the incoming air 
(See diagram 1).  

 

All coils have one or more circuits. Circuits are added to reduce the water pressure drop to an 
acceptable  level  (usually  10-ft.  H²O  pressure  drop  or  less).    Due  to  the  various  circuit  options 
available, the inlet, and outlet may change position making the inlet and outlet locations vary. 

 

Four-Pipe Coils  

Four-pipe coils have a dedicated, chilled-water coil, and a dedicated hot-water coil, each with its’ 
own inlet and outlet, equaling four pipes.  All coils have a common tube sheet for four-pipe coils.  
Example:  A four-row, chilled-water coil and a one-row, hot-water coil would use a five-row coil 
with four rows for chilled-water and one row for hot-water.  Normally the one-row, hot-water coil 
is in the reheat position or downstream from the cooling coil.   The hot-water coil may also be 
ordered in the preheat position or upstream from the chilled-water coil. The controls are wired so 
that either the chilled-water coil is operating or the hot-water coil is operating, but not both at the 
same time.  When the conditioned space thermostat is satisfied, both the chilled- and hot-water 
control valves are deactivated.  The same rule applies for inlet and outlet locations as explained 
above  in  “Two-Pipe  Coils”  (See  diagram  2).    Each  chilled-  and  hot-water  coil  is  controlled 
individually so a pipe sensor is not required. 
 

Hose Kits 

When hose kits are being used on units it is important to make sure the hoses are not installed 
over any electrical components, such as j-boxes, actuators, etc.  Hoses are not sweat proof so 
they can condensate. It is recommended that the flex hoses be field insulated during installation. 
Failure to follow these directions may cause unit operation failure. 

 
Coil Identification 

The  following  diagrams  indicate  the  number  of  rows  and  type  of  chilled-  and  hot-water  coils.  
Standard coil has the hot-water coil located in the reheat position. 
 
 
 
 

 

 
 
 
 
 
 
 
 
 

 
 
Because of the variations of circuiting available, the location of the inlet and outlet connections 
may  vary  up  and  down.    However,  always  use  the  following  rule  to  be  correct.   

The inlet is 

always the lower connection and the farthest away from the entering-air-side.  The outlet 
connection is always the higher connection closest to the entering-air-side. 

Содержание VW series

Страница 1: ...Installation Operating Maintenance Instructions Vertical Models VW ...

Страница 2: ... Team about any problems or conditions that you do not understand Safety Symbols and Labels used in these instructions Receiving Upon delivery examine each unit carefully for shipping damage Immediately report any freight damage to the freight carrier and file a freight claim with the carrier All units are shipped FOB factory therefore The Whalen Company is not responsible for damage during transi...

Страница 3: ...the building drain The Whalen Company will not assume any liability for damage caused as a result of the condensate drain line not being properly pitched or trapped The use of a secondary drain pan under the entire unit with a separate drain line is advised in areas where water damage is very critical See the Fan Coil Piping Instructions on Page 5 CAUTION It is the sole responsibility of the custo...

Страница 4: ... the Valve Stem Marking as shown If not pivot the gray Release Lever and while pivoted turn the large black lever accordingly 3 Set both dip switches in the position toward the black lever 4 Place the green actuator assembly onto the valve and re insert the pins Fan Coil Piping Instructions CHILLED AND HOT WATER COILS Purpose This data is intended to explain piping arrangements for chilled and hot...

Страница 5: ...e chilled water coil is operating or the hot water coil is operating but not both at the same time When the conditioned space thermostat is satisfied both the chilled and hot water control valves are deactivated The same rule applies for inlet and outlet locations as explained above in Two Pipe Coils See diagram 2 Each chilled and hot water coil is controlled individually so a pipe sensor is not r...

Страница 6: ...e not to bend or damage the fin surface After brushing the coil should be vacuumed to remove loose dirt o Check insulation for proper coverage to maintain efficiency and prevent sweating o Piping inspect all connections for leaks and corrosion o Valves Check for proper operation corrosion and leaking Motor Annually o If there are no oil tubes present the motor is permanently lubricated o If oil tu...

Страница 7: ...r and recorded on the Filter Replacement Log Once before the heating season and once before the cooling season Periodic checks should be made during the cooling season to insure that excessive dust or lint is not accumulating to the extent of interrupting free air flow If excessive dirt accumulates the filter should be changed more frequently o Reusable Cleanable Filters should be thoroughly clean...

Страница 8: ...8 Maintenance Repair Log Address Unit No Model Description Model No Serial No Voltage Amps Start Up Date Date Descriptionof Service Parts Required Signature ...

Страница 9: ...9 Filter Replacement Log Address Unit No Model Description Model No Serial No Replacement Date Signature Replacement Date Signature Replacement Date Signature ...

Страница 10: ...upply Voltage 17 Proper Steam Supply Pressure To Unit 15 PSI Max 45 Record Ambient Temperatures 18 All Services To Unit In Code Compliance 46 Check All Wiring For Secure Connections 19 All Shipping Screws Brace Removed 47 Close All Unit Isolation Valves 20 Unit Protected From Dirt Foreign Matter 48 Flush Water Systems 21 Filter Is Clean Free Of Construction Debris 49 Fill Systems With Water Refrig...

Отзывы: