Table 3
Module
p/n
LED State
Indicates
Off
There is no power applied to the device.
Green
Device is operating in a normal condition.
Flashing Green
The device Needs commissioning due to
configuration missing, incomplete or incorrect.
Red
Unrecoverable fault, device may need replacing.
Module
Status
LED 1
Flashing Red
Recoverable fault.
Off
Not powered/ Not online
Green
For a Group 2 Only device: Device is allocated to
Master
Flashing Green
Online, not connected. For a Group 2 Only device:
Device is not allocated to a Master
Red
Failed communication device. The device has
detected an error that has rendered it incapable of
communication on the network (Duplicate MAC ID
or Bus-off).
Network
Status
LED 2
Flashing Red
One or more I/O connections are in the Time-out
state.
Closed LS
IN_0 LED
Yellow
Input 0, Bottom L.S. Closed
: Valve is in the
closed position as determined by the triggering of
the Internal Hall Effect sensor by the travel of the
trigger mechanism on the shaft assembly.
Open LS
IN_1 LED
Yellow
Input 1, Top L.S. Closed
: Valve is in the open
position as determined by the triggering of the
Internal Hall Effect sensor by the travel of the
trigger mechanism on the shaft assembly.
Aux. Input
IN_2 LED
Yellow
Input 2, Active:
Dry contact type switch attached
to this input is closed.
Aux. Input
IN_3 LED
Yellow
Input 3, Active:
Dry contact type switch attached
to this input is closed.
Output
OUT_0
LED
Yellow
Output 0
. “A” Solenoid is energized.
EL-
40092
Output
OUT_1
LED
Yellow
Output 1
. “B” Solenoid is energized.
Tech-309
1-6