![Westlock Controls Corporation Intellis 7604 Скачать руководство пользователя страница 37](http://html1.mh-extra.com/html/westlock-controls-corporation/intellis-7604/intellis-7604_installation-and-operation-manual_965880037.webp)
Tech-309
- 13 -
Connection Object
Instance #2
Attributes
(Poll I/O connection - Instance #2)
Class=5, Instance=2, Attribute=1-17
Attr.
ID
Access
Rule
Name
Data Type
Value
1
Get
State
USINT
0x01 0x03 or 0x04
2
Get
instance_type
USINT
0x01 (1 is poll I/O)
3
Get
transportClass_trigger
BYTE
0x82 (server class2)
4
Get
produced_connection_id
UINT
011 11xx xxxx binary
xx xxxx source -slave MacID
5 Get
consumed_connection_id
UINT
10x xxxx x101 binary
x xxxx x destination-slave MacID
6 Get
initial_comm_characteristics USINT
0x01
(0x00 - Produce Group1 Msg.)
(0x01 – Consume Group 2 Msg.)
7 Get
produced_connection_size UINT
0x0001
8 Get
consumed_connection_size UINT
0x0001
9 Get/Set
expected_packet_rate
UINT
Application
Dependent
10
N/A
N/A
N/A
Not Used
11
N/A
N/A
N/A
Not Used
12
Get
watchdog_timeout_action
USINT
0x00 (Time Out- default for I/O)
13 Get produced_conn_path_length UINT
0x0006
14 Get produced_connection_path
segment type . format
value(logical.classID.8bit)
segment type .format
value(logical.instanceId.8bit)
segment type . format
value(logical.attributeId.8bit)
STRUCT
of
USINT
USINT
USINT
USINT
USINT
USINT
0x20.0x04.0x24.0x04.0x30.0x03
fields---------explaination-----------
0x20 logical.classID.8bit address
0x04 (Class 4 - Assembly)
0x24 logical.instanceID.8bit addr
0x04 (Instance #4 - 8 Inputs)
0x30 logical.attributeID.8bit addr
0x03 (Attribute 3 - Data)
15 Get consumed_conn_path_length UINT
0x0006
16 Get consumed_connection_path
segment type . format
value(logical.classID.8bit)
segment type .format
value(logical.instanceId.8bit)
segment type . format
value(logical.attributeId.8bit)
STRUCT
of
USINT
USINT
USINT
USINT
USINT
USINT
0x20.0x04.0x24.0x21.0x30.0x03
fields---------explaination-----------
0x20 logical.classID.8bit address
0x04 (Class 4 - Assembly)
0x24 logical.instanceID.8bit addr
0x21 (Instance #33 - 4 Outputs)
0x30 logical.attributeID.8bit addr
0x03 (Attribute 3 - Data)
17 Not
Supp.
Production_inhibit_timer
UINT
(Server devices do not use this timer)
Common Services - (
Instance #2
)
Service Code (Hex)
Service Name
Description of service
0x0E
Get_Attribute_Single
Returns the contents of the specified attribute
0x10
Set_Attribute_Single
Modifies the contents of the specified attribute
0x05
Reset
Reset Inactivity/Watchdog Timer, if connection is in
“Timed Out” state changes to “Established” state.
Содержание Intellis 7604
Страница 17: ...Tech 309 2 7 ...
Страница 18: ...2 4 1 DPAC Connector Pin out Diagrams Tech 309 2 8 ...