![Westlock Controls Corporation Intellis 7604 Скачать руководство пользователя страница 15](http://html1.mh-extra.com/html/westlock-controls-corporation/intellis-7604/intellis-7604_installation-and-operation-manual_965880015.webp)
2.3 Switch Adjustment
Switches are factory set. If you need to adjust switches for any reason follow
instructions below.
For steps 1-8 refer to Figures 1 and 5.
1.
Refer to Figure 1 and note the approximate locations of the Open and Close
targets on the DPAC module.
2.
With the valve in the closed position, lift bottom cam of the Close sensor trigger.
3.
Turn cam until face of trigger is perpendicular to the target and sensor is activated
as evidenced by the lighting of the corresponding module LED.
4.
Release the cam and the spring will push cam back onto the splined shaft.
5.
Operate the actuator to the opened position.
6.
Push down the top cam of the Open sensor trigger.
7.
Turn cam until face of trigger is perpendicular to the target and sensor is activated
as evidenced by the lighting of the corresponding module LED.
8.
Operate actuator from one extreme to the other several times to check Limit
Sensor operation.
Figure 5
Tech-309
2-5