TY P E S I R P, I RC AND I R D R E LAYS
R E LAY RAT I NG
All Ranges
All Ranges
TABLE I I
D I R ECTIONAL UNIT CAL I B RATION
t
CURR ENT AMP E R E S
BOTH PLUGS I N COND I T I ON
80
Spurious Torque In Contact
Closing Direction (Left Front
View)
80
Spurious Torque In Contact
Opening Direction (Right Front
View) (Contacts remain open)
ADJUSTMENT
Right (Front-View) Plug Screwed
Out Until Spurious Torque is Re-
versed.
Left (Front View) Plug Screwed
Out Until Spurious Torque is in
Contact Closing Direction. Then
the plug is screwed in Until Spuri-
ous Torque is Reversed.
t
Short circuit the voltage polarizing circuit at the relay terminals before making the above adjustment.
TAB L E I l l
T I M E C U R V E C AL I B R A T I O N D A T A - 60 C Y C L E S
PERMANENT MAGNET ADJUSTMENT
ELECTROMAGNET PLUGS
TIME-
TIME
CURRENT
OPERATING
CURRENT
OPERATING
OVERCURRENT
DIAL
(MULTIPLES OF
TIME
(MULTIPLES OF
TIME
UNIT TYPE
POSITION
TAP VALUE )
SECONDS
TAP VALUE)
SECONDS
2
6
3
0.57
2 0
0.22
5
6
2
37.80
1 0
14.30
6
6
2
2.46
2 0
1 . 19
7
6
2
4.27
2 0
1 . 1 1
8
6
2
13.35
2 0
1 . 1 1
9
6
2
8.87
2 0
0.65
1 1
6
2
1 1. 27
20
0 . 24
28
www
. ElectricalPartManuals
. com