TY PES I R P , I R C AN D IRD R ELAYS
ENE RGY R EQUI R EMENTS
-
60
CYCLES
D I R E CT I O N A L U N I T O P E R AT I N G C I R C U I T B U R D E N
VOLT AMPERES* *
At
At 3 Times
At 10 Times
At 20 Times
Continuous
One Second
Power
Minimum
Minimum
Minimum
Minimum
Relay
Range
Rating
Rating *
Factor
Tap Value
Tap Value
Tap Value
Tap Value
Type
Amps
(Amperes)
(Amperes)
Angle
¢
Current
Current
Current
Current
0 . 5-2.5
230
44. 0
0 .033
0 . 30
3 . 3
14 . 2
IRC
2-6
230
42.5
0. 58
5 . 28
58.0
240 . 0
4-12
1 2
280
3 1 .8
0. 64
6. 12
70 .0
272.0
0.5-2.5
10
230
34.5
0. 03
0 . 23
2.8
1 1 . 5
IRP
2-6
10
230
34.5
0 . 44
4.08
48.0
182 . 0
4- 12
1 2
280
25.0
0 .48
4 . 62
53.6
216.0
0.5-2.5
10
230
45.0
0. 07
0.5
9
6. 6
26.0
IRD
2-6
10
230
45. 0
1 . 04
9 . 9
106. 0
420.0
4- 12
12
280
32. 4
1 . 16
10.8
1 2 1 . 2
472.0
¢ Degrees cu"ent lags voltage at tap value current.
•
Thermal capacities for short times other than one second may be calculated on the basis of time b eing
inversely proportional to the square of th e cu"ent.
• •
Voltages taken w ith Rectox type voltmeter.
R E L AY T Y P E
IRC'
IRP
IRD Current
Unit
IRD Voltage
Unit
ENE RGY R EQUI R EMENTS
-
60
CYCLES
D I R ECT IONAL UNIT POLARI Z I N G CI RCUIT BURDEN
R AT I NG
VOLT AMP E R ES
t:,
230*
1.45
Amperes
208* *
1 1 . 2
Volts
230*
1.45
Amperes
208 * *
1 1 . 2
Volts
POW E R FACTOR ANGL E ¢
8° Lag
28° Lead
8° Lag
28° Lead
¢
Degrees current leads or lags voltage at 120 volts on voltage polarized units and 5 amperes on current
polarized units ..
8
1::,
Burden of voltage polarized units taken at 120 volts. Burden of current polarized units taken at 5 amperes.
* One s econd rating.
* * 30 second rating. The 10 second rating is 345 volts. The continuous rating is 1 20 volts.