TYPE I RQ R ELAY
c
STATION !US
PHASE ROTATION
1 , 2 , 5
67N
.--
6 7 N
-.---
67N
-or
67N
67N 67N
li"" IT 16
!CS
T
67N
TO
67N
67N
DEVICE NUMBER CHART
liST
SEC.
CONTACT
CLOSES
67N
DIRECTIONAL OVERCURRENT NEGATIVE
SEQUENCE GROUND REL AY, TYPE IRQ
I
I
I
D
- DIRECTIONAL UNIT
CO - T I M E - OVERCURRENT UNIT
D IRECTIONAL UNIT
PHASE
ANGLE
CHARACTERISTICS
I
- INSTANTANEOUS O;C U N I T
I ! S T - SATURAT I N G TRANSFORMER
FOR INSTANTANEOUS 0/C UNIT
ICS - IND ICATING C O N TACTOR SWITCH
CS-1
-
A U X I L I A R Y CONTAGTOR SWITCH
I
2 3
I
I
I
I
I
5A
I
-
67N
61N
1 5;5
PRI.
ALTERNATE
CONNECTION
( NEUTRAL FORMED
EXTERNAU.Y)
52
POWER CIRCUIT BREAKER
U
-
A U X I L I A R Y CONTACT
TC - TRIP C O I L
290:8551
* Fig. 1 1 . External Schematic of I R Q Relay.
The external connections of the directional
overcurrent relay are shown in Fig. 12.
A D J U S T M E N T A N D M A I N T E N A N C E
The proper adjustments to insure correct op era
tion of this relay have been made at the factory. Upon
receipt of the relay, no customer adjustments, other
than tho se covered under "SETTINGS" , should be
required.
A c c e p ta n c e C h e c k
The following check is recommended t o insure
that the relay is in proper working order;
N e g a t i v e S e q u e n c e F i l t er
The filters are adj usted for balance in the factory
and no further adjustments or maintenances should be
required. The nominal voltage and current output of
the filters on po sitive sequence i s approxiruately zero.
This serves as a convenient check on the balance of
the filters. If any two input l eads to the potential
filter should be interchanged, a high voltage occurs
across the output terminals of the filter. Similarly,
if any two of the phase l eads to the input terminals
of the current filter are interchanged, an output cur
rent will be obtained.
D i r e c t i o n a l U n i t ( D )
1 . Contact Gap - The gap between the station
ary contact and moving contact with the relay in the
de-energized position should be approximately . 0 20"
2.
- R efer to the test diagram in fig.
1 2. Apply a single-phase voltage V 12 equal to 0 . 5 7
volts ( corresponds t o a negative-sequence input
voltage of
.
19 volts) and a single-phase current equal
to 6. 93 amperes as shown ( corresponds to a negative
sequence input current of 4 amperes). With a phase
angle meter connected as sho wn, rotate the phase
shifter until the current leads the voltage by 188°.
This corresponds to the negative sequence component
of current leading the negative sequence component
of voltage by 98 °.
The directional unit contact
9