background image

Contact  Assembly 

The  contacts  should  be  checked  periodically  for  wear  and 

adjustment.  Under  normal  conditions,  the  contacts  should  be 

good  for  a  large  number  of  operations.  A  small  amount  of 
surface pitting on  the main contacts will not impair the normal 
current carrying capacity of the breaker. Any excess roughness 
can be smoothed with fine aluminum oxide paper making cer­
tain  that  at  least  70%  of  the  line  contact  surface  is  effective. 

The  arcing  contacts  are  subject  to  the intense  heat  of  the  arc 

when interrupting current. Each arc interruption will burn away 
some of the arcing contact metal.  When they have reached the 
point where  only 

Va 

inch of  contact  material  remains,  the  con­

tact  block  or  moving  contact  finger  should  be  replaced. 

The  moving  contact  assembly  is  illustrated  in  Fig.  6. The  fol­
lowing steps are necessary to remove the complete assembly 
from the breaker  for servicing: 

1.  Remove  the  pin  A,  Fig.  3,  which  disconnects  the  toggle 

linkage. 

2.  Remove the  pin  fastening  the  opening  spring  guide  to  the 

top of  the contact arm casting.  Remove pinT,  Fig. 3. 

3.  Remove the bolts holding the hinge block to lower stud. 

4.  Lift the contact assembly out of the  breaker. 

Adjustments 

Contact  Adjustment 

To completely re-adjust the contacts, start by loosening the bolts 

holding  the stationary  arcing  contact  and  backing  off  the  jack 
screw  so  that  the  contact  is  free  to  slide  back  on  the  upper 
stud.  It is best to make the following adjustments with the lock­
ing-bar in place as shown in  Fig.  4.  If a locking-bar is not avail­
able,  then the holding coil must be energized with 200mA D.C. 
current. 

Make  certain  that  the  armature  does  not  pull  away -from  the 
holding  magnet as the  breaker  is closed. 

Contact adjustments should be started by checking the com­

pression of the  main  contact  finger  springs on each  side  of 
the moving contact arm assembly. This can be done by com­
paring  the  measurements  of  dimension 

L, 

Fig.  3,  with  the 

breaker  open  and  with  it  closed. The  main  contact  spring 
compression should be .063±.020 as indicated by the differ­
ence in  dimension  L.  If these measurements  are not within  tol­
erance,  open  the  breaker,  loosen  the  lock  nut  on  the  eccentric 
pin  D,  Fig.  3,  and  ascertain  that  the  eccentric  is  down  and  for­
ward  (closer  to  pole  unit). The  exposed  right-hand  side  of  the 
pin  has  been  machined  to  indicate  location. Turn  the  pin 

clockwise to decrease the spring compression, or counter-clock­
wise to increase it. In general, only a few degrees of rotation will 
be  required.  Lock the  eccentric pin and close the  breaker to re­
check the  main contact finger spring compression. 

The  next  adjustment  to  be  checked  is  the  length  of  the  pull 

rod 

G, 

Fig.  3,  which  controls  the  amount  that  pin  C  moves 

over toggle.  If  pin C moves too far  over  toggle position,  then 
the  contact  arm  will  close  and  then  re-open  slightly  as  the 

closing  handle  reaches  its final  closed  position.  If pin  C does 

not move far enough,  then the breaker will tend to slam  open 
during  electrical  closing. The  pull  rod  length  should  be  ad­
justed  so  that  the  operator  can  feel  a  definite  snap  as  pin  C 
goes over  toggle,  but  cannot  notice  any return  motion of the 
moving  contact  support. The  correct  adjustment is  1112  turns 
over  toggle. 

The pull rod length can be adjusted, if necessary,  by loosening 

the lock nut  R,  removing pin 

Q, 

and rotating the universal joint 

P  to  shorten  or  lengthen  the pull  rod  assembly. The universal 

joint  has  R.H.  threads.  After  adjustment.  place  a  screw-driver 
blade  between  the  frame  of  the  universal  joint  and  the inside 
of the slot in the closing solenoid plunger to keep the universal 
joint  centered  in  the  slot,  and  tighten  the  lock  nut  R.  Recheck 
main  contact  spring  compression. 

The  stationary  arcing  contact  should  be set  last.  This can  be 

done by closing the breaker by hand until a  1/8-inch shim can 
be placed between the main  contacts at  dimension  M,  Fig. 3, 
and moving the stationary arcing contact forward until it just 

touches the  moving arcing contact. Then tighten the  mount­

ing  bolts  on  the  stationary  arcing  contact.  Re-check  the  gap 
between the main contacts to make certain  that  the  1/8 shim 
is  a  snug fit when the arcing tips  just touch. 

As a final check, the breaker should be tested for electrical clos­
ing  and  for  holding  coil  drop-out.  The  breaker  should  be  ca­
pable of closing at  100 volts  and  as high as  140  volts  without 
slamming  out. The  closing  voltage  figures  are  obtained  by 

measuring  the  closing  coil cold  resistance  and  multiplying  it 
by  the  measured  closing  coil  current. This  method  must  be 
used since the closing coil resistance will change due to heat­
ing and make measured closing coil voltages meaningless. The 
closing coil current times the cold  coil resistance will give  the 
voltage conditions corresponding to the initial operation of the 
breaker regardless of the present temperature of the coil.  Dur­
ing electrical closing tests,  the closing coil  should be checked 
occasionally to make sure that it does not reach temperatures 
high enough to burn out the coil.  This coil  is intended for mo­
mentary  duty  only and  should  not have  a  current  applied  for 
more than a few seconds at a time. 

The  drop-out  can  be  checked  by  connecting  the  holding  coil 
to  a  source  of  variable  direct  current.  Set  the  current  to  200 

milliamperes and close the breaker.  Reduce the current slowly 
until the breaker opens.  The measured value of current should 

be  within  the  range  of 32  to  100  milliamperes.  If  the  drop-out 
current  is  not  within  these  limits,  re-check  the  breaker  adjust­
ments.  If adjustments are properly made and the drop-out cur­

rent is still not within tolerance,  the factory should  be consulted. 

lubrication 

All pins and bearing surfaces except the moving contact hinge 
joint are coated  at the factory  with molybdenum disulphide.  If 
the  breaker  linkage  is  dismantled,  the  pins  and  bearing  sur­
faces  should  be  wiped  clean  and  coated  with  molybdenum 
disulphide dissolved in alcohol and applied with a small brush. 
The  alcohol  will  evaporate  rapidly  and  leave  a  deposit  of 
molybdenum disulphide on  the  surface. 

The  moving  contact  hinge  joint  must  be  lubricated  only  with 

a  good  grade  of  graphite  grease  such  as  WEMCO  PDS  1022-
1. Do not apply molybdenum disulphide to the moving contact 

hinge joint, since this lubricant is not a good electrical conductor. 

/.B.  201 

www 

. ElectricalPartManuals 

. com 

Содержание De-ion DM2F

Страница 1: ... Breakers Types DM2R DM2F Westinghouse Electric Corporation Renewal Parts and Specialty Products 820 Washington Boulevard Pittsburgh Pennsylvania 15206 Effective February 1994 I B 201 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 2: ...cular information is desired be sure to state fully and clearly the problem and attendant conditions giving the figure showing parts in question and using names for the parts as given Address all communications to the nearest Westinghouse Sales Office For a permanent record it is suggested that all nameplate data be duplicated and retained in a convenient location w w w E l e c t r i c a l P a r t...

Страница 3: ...justment 6 Lubrication 6 Operating lrregularities 7 Pole Units Failing to Close 7 Holding Armature Fails to Hold 7 Breaker Slams Open When Closing 7 Renewal Parts Identification 7 1 8 201 List of Illustrations Figure Page Diagram of Breaker Operation with Bucking Bar 2 Schematic of Current Interruption 2 3 Schematic of Operating Mechanism 2 4 Use of Locking Bar 3 5 Polarity Hookups 4 6 Moving Cont...

Страница 4: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Страница 5: ... The bucking bar inductive shunt combination consists of a small bucking bar passing through the holding magnet and a lami nated iron circuit around the lower stud to force additional current through the bucking bar on high rates of rise The cur rent through the bucking bar under normal conditions is small and has very little neutralizing affect on the holding coil mag netic circuit Adjustments ar...

Страница 6: ...p by the holding coil As the bucking bar current rises the resultant flux through the armature will be reduced to a value that permits the armature to be pulled away by the spring load on the linkage and the breaker will open As the breaker starts to open the main contacts part first and cause the current to flow through the arcing contacts as shown on Fig 2 The arcing contacts then part and an ar...

Страница 7: ...s to pull away from the holding magnet when the breaker is closed then the forcing screw must be re tightened However the breaker must always be in the open position when adjusting the forcing screw For closing tests about 30 amperes at 125 V D C should be supplied to the closing coil of each pole unit tested The cur rent must not be applied for more than a few seconds at a time since the closing ...

Страница 8: ...2F Feeder Breaker with upper stud negative lower stud positive Polarity Connection Factory Connection I 7 Breaker J t 4 F_H_ C 1 Holding Coil 4 1 4SHC 7 Breaker J 6 t 5 F TC 1 Tripping Coil 5STC 5 I Terminal Block on Breaker Forward Trip DM2R Rectifier Breaker with upper stud positive lower stud negative Polarity Connection 3 Factory Connection I 4SHC 7 Breaker t 1 f 4 F_H _ C 1 Holding Coil 1 t t...

Страница 9: ...shing cloth or very fine emery paper with the grit side up on a surface plate Lay the ar ature n the polishing cloth and move it about carefully w1th a c1rcular motion until all high spots are removed 1 8 201 Fig 7 ARC Chute CAUTION The arc chamber contains ceramic material Handle carefully Do not drop tip over or bump Insulating parts of the arc chamber must withstand more than the full line pote...

Страница 10: ...n C goes over toggle but cannot notice any return motion of the moving contact support The correct adjustment is 1112 turns over toggle The pull rod length can be adjusted if necessary by loosening the lock nut R removing pin Q and rotating the universal joint P to shorten or lengthen the pull rod assembly The universal joint has R H threads After adjustment place a screw driver blade between the ...

Страница 11: ... 2 Armature or holding magnet surface is not flat 3 Poor connection in the holding coil current Breaker slams open when closing 1 Improper adjustment of toggle links 2 Faulty holding magnet or armature 10 Special Inquiries When communicating with Westinghouse regarding the product covered by this Instruction Book include all data contained on the nameplate attached to the equipment Also to facilit...

Страница 12: ...1 8 201 Printed in U S A w w w E l e c t r i c a l P a r t M a n u a l s c o m ...

Отзывы: