WESTFIRE · WF
32
18
trOuBLe sHOOting
1. fire will not burn – check
a) the air inlet is not obstructed in any way,
b) that chimneys and flueways are clear,
c) that a suitable fuel is being used,
d) that there is an adequate air supply into the room,
e) that an extractor fan is not fitted in the same room as the fire.
2. fire blazing out of control – check
a) the doors are tightly closed,
b) the air controls are turned down to the minimum setting,
c) the air controls are closed and not prevented from closing completely by a piece of ash,
d) a suitable fuel is being used, use only hard wood. NO WASTE WOOD.
e) the door seals are in good condition.
f) if the chimney draft may be too strong
g) if ash pan seal is in good condition
h) for ash below ash pan causing pan to not seat correctly and clean out.
3) soot forms on the window
a) The firewood may be too wet
b) the intake of secondary air may be insufficient
c) fire not hot enough
4) the stove fails to heat fully
a) The firewood may be too wet
b) the intake of secondary air may be insufficient
5) smoke or odour
a) Weak chimney draft
b) check for blockages in the flue pipe/chimney
c) check the height of the chimney in relation to the surroundings
6) soot in the chimney
a) The firewood may be too wet
b) intake of secondary air may be insufficient
Chimney fires
If the chimney is thoroughly and regularly swept, chimney fires should not occur. However, if a chimney fire does
occur turn the air control setting to the minimum, and tightly close the doors of the stove. This should cause the
chimney fire to go out in which case the control should be kept at the minimum setting until the fire in the stove
has gone out. The chimney and flue ways should then be cleaned. If the chimney fire does not go out when the
above action is taken then the fire brigade should be called immediately.
After a chimney fire the chimney should be carefully examined for any damage. Expert advice should be sought
if necessary
Permanent air vent
The stove requires a permanent air vent to the room or a direct connection to the closed air port at the rear of the
stove. This is to provide adequate air supply in order for the stove to operate safely and efficiently.
In accordance with current Building Regulations the installer may have fitted a permanent air supply vent into the
room in which the stove is installed to provide combustion air. This air vent should not under any circumstances
be shut off or sealed.
aerosols
Aerosols are flammable and therefore dangerous to use around a lit stove. Do not use aerosols sprays near your lit
stove. The use of any aerosol is dangerous and care must be taken in handling aerosols.
uk
Содержание WF32/UNIQ32 Freestanding
Страница 31: ......