12
6650-2201
Optical Power Budget
The maximum supported link lengths as specified in table above should only been seen as
indicative.The allowed link length is calculated from the Optical Power Budget (OPB), the
available optical power for a fibre-optic link, and the attenuation of the fibre, comprising
losses due to in-line connectors, splices, optical switches and a margin for link aging
(typical 1.5 dB for 1300 nm).
The worst-case Optical Power Budget (OPB) in dB for a fibre-optic link is determined
by the difference between the minimum transmitter output optical power and the lowest
receiver sensitivity.
Fibre connector
LC duplex
LC duplex
LC duplex
LC duplex
Fibre type
Singlemode
Singlemode
Singlemode
Multimode,
9/125 mm
9/125 mm
9/125 mm
62.5/125 and
50/125 mm
Wavelength
1550 nm
1310 nm
1310 nm
1310 nm
Transmitter
–5/0 dBm
–5/0 dBm
–15/–8 dBm
–20/–14 dBm
Output optical power min/max
**
**
**
*
Receiver
–34 dBm
–34 dBm
–31 dBm
–31 dBm
Input sensitivity
(max)
(max)
(max)
(max)
Receiver
–5 dBm
–3 dBm
–8 dBm
–8 dBm
Input optical power Maximum
(min) ***
(min) ***
(min)
(min)
Bit error rate (BER)
<1 x 10
–10
<1 x 10
–10
<1 x 10
–10
<2.5 x 10
–10
Transceiver type
Small Form Factor Pluggable (SFP)
Multi-Sourcing Agreement (MSA) compliant
Laser class
Class 1, IEC 825-1 Accessible Emission Limit (AEL)
FX (Fibre)
SM-LC80
SM-LC40
SM-LC15
MM-LC2
*
Output power is power coupled into a 62.5/125 mm multimode fibre.
**
Output power is power coupled into a 9/125 mm singlemode fibre.
*** The optical power should be reduced by at least 5 dB (SM-LC80)
or 3dB (SM-LC80) between the optical output and input.
Electrical specification
EIA RS-485 / EN 50 170
Data rate
9 600 bit/s, 19.2, 93.75, 187.5, 500 kBit/s, 1.5, 3, 6 and 12 Mbit/s
Data format
8 data bits, even parity, 1 stop bit, 11 bits total
Protocol
PROFIBUS DP / EN 50170
Data Rate detection
Yes, compliant with EN 50 170
Retiming
Yes
Turn around time
In accordance with EN 50 170
Transmission range
≤
1200 m, depending on data rate and cable type (EIA RS-485)
Settings
None, external termination and failsafe biasing
Protection
Installation Fault Tolerant (up to ±60 V)
Isolation to
Power and Status port
Connection
9-pin D-sub female
Shielded cable
Not required
Conductive housing
Isolated to all other circuits and housings
PROFIBUS DP (RS-485)