background image

GB.ModemIN.120619

www.swegon.com     1

We reserve the right to alter specifications.

Installation instructions for the
TBLZ 2-3-41-2 and TBLZ 2-3-41-1 modem
GOLD

1. General

The SRT DIN 35 and the Siemens MC35i/MC52i modems 
are intended to be used for the GOLD RX/PX/CX/SD air 
handling units, Version C and D.
The SRT DIN35 is designed the analogue telecom network; 
Siemens MC35i/MC52i is designed for the GSM network.

2. Safety precautions

Be careful when you connect various cables to the unit. 
Never carry out work while the mains power supply is con-
nected. Doing so may harm the unit. Observe local electri-
cal safety regulations as you install the unit.
Find out before you install the modem whether the SIM 
card requires PIN code entry. This will prevent the SIM card 
in the GSM modem from locking if an erroneous PIN code 
is entered. If that is the case, enter the correct PIN code via 
the webpage for the relevant GOLD air handling unit. This 
is described in more detail in the Webpage Manual.

3. Analogue modem, SRT DIN 35,
TBLZ-2-3-41-2

3.1 Description

The modem is supplied packaged in a box containing the 
following

:

1. 

 SRT DIN35 modem with 3-pole power socket

2.

  Telecom cable. 6/4 RJ11 modular connectors

3.

  Interface cable. 9-pin D-sub connector modular  

 connector 

4.

  Telephone plug for Sweden, if a plug for other country  

 

is desired, it must be purchased separately.

5.

  CD ROM containing complete user’s manual in   

 

Swedish and English. 

6.

  A concise installation manual in English.

 

The unit consists of:

1.

  6 module standard enclosure for DIN rail fastening  

 IP20.

2.

   9-pin D-sub connector for connection via

 

supplied interface cable for the EIA 232 port of the  

 

GOLD unit.

3.

  6/4 pole modular socket for connection to telecom  

 

jack via supplied telecom cable.

4. 

 Power socket for 10-24 V AC/DC,

 

25 mA at 24V DC supply.

5. 

 LEDs (CD, OH, RxD, TxD, PWR).

 

The indicating LEDS are described further on in these  

 instructions.

SRT DIN 35 Analogue modem, 

SIEMENS MC35i/MC52i 
GSM modem

1

5

4

2

3

Содержание TBLZ 2-3-41-2

Страница 1: ...e via the webpage for the relevant GOLD air handling unit This is described in more detail in the Webpage Manual 3 Analogue modem SRT DIN 35 TBLZ 2 3 41 2 3 1 Description The modem is supplied packaged in a box containing the following 1 SRT DIN35 modem with 3 pole power socket 2 Telecom cable 6 4 RJ11 modular connectors 3 Interface cable 9 pin D sub connector modular connector 4 Telephone plug fo...

Страница 2: ... modem The LEDs can be ON OFF or FLASHING to indicate the opera ting status of the modem The abbreviated captions of the LEDs are as follows PWR Power Modem is operational LIT The power is ON to the modem but the modem is not operating FLASH The power is ON to the modem and the modem is operating OFF The power is OFF to the modem OH Off Hook Line status LIT The line is busy the modem is off hook O...

Страница 3: ...ptional enclosure 2 Put in the SIM card in the SIM card holder with the connector surfaces upwards Push in the holder into the modem 3 Fit the antenna cable in intended connector of the modem Fasten the antenna outside the GOLD unit for best communication 4 Plug the 9 pin D sub connector of the interface cable into the corresponding socket of the modem 5 Plug the other end of the interface cable i...

Страница 4: ...m IMPORTANT All SIM card subscriptions do not support data communication Check with your GSM operator In order to hook up to the unit with the modem and have access to its webpage the settings must be as shown in the menu below in most cases these values have already been filled in at the factory The GOLD air handling unit s settings can be entered by means of a computer that has been connected by...