Data Rate
The data rate can be set from 300 bit/s to 115.2 kbit/s.
Default is 19 200 bit/s.
Data Bits
Seven (7) or eight (8) data bits can be selected. Eight data bits is default.
Stop Bits
Two (2) stop bits can be set if no parity is selected.
Default is one (1) stop bit.
Parity
No, odd or even parity can be selected. No parity is default.
Flow Control
Flow control can be chosen between none or hardware. Hardware flow control is man-
aged by the CTS and RTS signal. CTS is switched off (<-3 V) when the ED-10 serial
receive buffer is near full. The buffer size is 5 kByte.
Serial data from ED-10 will be transmitted if the RTS is on (>3 V).
Flow control is ignored for port type RS-422/485.
Default, flow control is switched off (none) and the CTS will follow DSR.
Termination and Failsafe (Only by switches)
Termination and fail-safe is used for port type RS-422/485 and manually can be switched
on or off.
Switch pair S1:7,8 is used in 2-wire mode. In 4-wire mode switch pairs S1:5,6 are used.
Default is termination and failsafe switched off, i.e. all switch pairs off.
End of frame character, EoF Char
ASCII code of character indicating end of frame (0-255). The serial data buffered will be
sent over network when this character 0 - 255 is detected (e.g. 13 for Carriage return).
256 deactivates this function.
Allowed values are 0 – 256. Default is 256, i.e. deactivated.
Transmit end of frame character
Include end of frame character in Network data packet. Allowed alternatives are yes or
no, default is yes.