Expanding the Light Array System
6. Expanding the Light Array System
6.1 Relay Unit
The SG4-00VA000R2 relay unit is equipped with two failsafe floating relay outputs. The terminals are connected to
the load circuit. The use of a spark arrestor significantly increases the service life of the relay contact. Two-channel
redundant wiring must also be observed when the relay unit is utilized. Both contacts must be used for load cur-
rent control.
GEFAHR!
Response times are increased by 8 ms when the relay unit is used.
Schematic Diagram, Relay Unit Connection
4
2
6
1
3
5
7
8
SG4-00VA000R2
1
2
3
4
5
6
7
8
9
10 11 12
13
15 16
14
15
9
10
12
12
14
7
8
1
2
4
3
6
5
24 V
Contactor Monitor
Plug Receiver
Acknowledge
0 V
Signal Outpur
Earth/Shield
PLC
OSSD 2
OSSD 1
24 V
0 V
Relay Unit Terminal Assignments
Required system components:
1 × transmitter, 1 × receiver
1 × cable
1 × connector cable
1 × relay unit