IO-Link
7.1.5 Simulation Functions
This function simulates the behavior of the sensor regardless of the current status and measured value. This
can be used to check whether a plant in which the sensor is integrated reacts correctly to the data supplied
by the sensor and processes them accordingly.
If a measured value is specified, the sensor behaves as if the specified measured value corresponds to the
actual measured value. This means that the behavior of the outputs and status messages is simulated
according to the specified measured value.
In addition, the individual outputs and status messages can be simulated separately from the measured
value.
Function
Possible Settings
Default
Simulation Mode
On
Off
Off
Measured Value Test
Current measured value
Minimum to maximum measuring range
Current measured value
Output O Test
According to the measured value
P1PY107: 0 – 10 V
P1PY108: 4 – 20 mA
According to the measured
value
SSC1 Test
According to the measured value
On
Off
According to the measured
value
SSC2 Test
According to the measured value
On
Off
According to the measured
value
Status Messages
Test
Tests the individual status messages
According to the measured value
On
Off
According to the measured
value
NOTE!
• Output O1 is used for IO-Link communication in this function and cannot be simulated.
• The simulation mode ends automatically as soon as the supply voltage is interrupted.