Replace fire suppression links in hood
plenum:
each link is rated @ 212°F
Replace two (2) fire suppression
links at cooking appliance:
each link is rated @ 212°F
Max interval: 12 months
Replace fire damper fusible link:
rated @ 280ºF
Max interval: 12 months
THIS MAINTENANCE LOG MUST
BE KEPT
IN
A
PROTECTIVE COVER PERMANENTL
Y
A
TT
ACHED
T
OTHE
APPLIANCE
Log all repairs and recommendations on reverse side.
Any repairs, other than replacement of factory authorized parts, to the fire suppression plumbing system must be
subject to hydrostatic pressure testing.
Log
TEMP
Log
TEMP
Log Mfg DA
TE
Stamp
Log Mfg DA
TE
Stamp
IL2610
Inspect fire suppression detectors, all releasing devices for
actuation, fire suppressant tank liquid level
Max interval: 6 months
(discharge of fire suppressant not a part of this test
)