6. Setting of parameters
106082
– MRF-M2 -E - V0.7 - 23.04.2021
Page 29
to section 6.3
Level
“Cooling parameters 2” (P parameters)
Cooling start settings
Range
Def.
P61 Variations of the cooling start delay
for the first milk see section 7.7
0 .. 3
1
0: deactivated (without cooling start delay)
1: cooling start delay
2: Interval cooling boosts (power reduction by cycles)
3: Interval cooling boosts after switch-on delay
P62 Duration of cooling start delay
if [P61] = 1..3
0..999 min.
30
P63 „ON“ time cooling boost
if [P61] = 2, 3
1 .. 30 min.
5
P64 „OFF“ time cooling boost
if [P61] = 2, 3
5 .. 60 min.
20
P65 Number of cooling boosts
if [P61] = 2, 3
1 .. 50
5
Compressor settings
Range
Default
P71
Minimum pause time compressor
(Pendulum protection)
Prevents the compressor from running against
pressure. The LED compressor is flashing dur-
ing the pause time.
0 .. 999 sec.
60
P72
Thermo protection and fault monitoring
compressor See also section 7.4
(Only possible if digital input [A21 = 5]
0 .. 4
0
0: deactivated
Evaluation of motor protection relay or motor protection switch
1: Thermal protection high-activated (error "F53" when open)
2: Thermal protection low-
active (error „F53" when closed)
Evaluation of auxiliary contact compressor contactor
3: Fault monitoring through switch-on feedback from the compressor
contactor normally open contact.
4: Fault monitoring through switch-on feedback from the compressor
contactor normally close contact.
Choice 3 or 4:
When a compressor is switched on, feedback is expected at the digi-
tal input after 60 seconds at the latest.
If this feedback does not come, fault F53 is triggered.