Installation and operating instruction
Hydraulic unit WWP LS 8 ... 16-B
6 Operation
83306902 2/2017-05 La
54-88
6.7.4.6 Flange heating
Domestic hot
water
Flange heating
The menu is only displayed in the Expert level.
Parameters
Setting
Change-over temperature
Release temperature for flange heating in the domestic water storage tank.
If the temperature in the storage tank exceeds
change-over temperature
set and if the DHW setpoint temperature has not been reached, the flange heating
takes over the entire DHW loading. The heat pump switches off or changes over
to heating mode.
Switch differential
Switch-off hysteresis for flange heating.
If the DHW temperature drops below the
change-over temperature
by the
switch differential
set, the flange heating switches off and the heat pump
tales over DHW loading.
6.7.4.7 Reset
Domestic hot
water
Reset
The menu is only displayed in the Expert level.
Reset all changes made in the DHW menu to factory settings.