Installation and operating instruction
Hydraulic unit WWP LS 8 ... 16-B
4 Installation
83306902 2/2017-05 La
21-88
4 Installation
4.1 Installation conditions
Dimensions
Observe dimensions [ch. 3.4.9].
Installation location
Prior to installation ensure that:
the installation location is frost free,
the bearing capacity of the wall is sufficient [ch. 3.4.8],
the space for the hydraulic unit is sufficient [ch. 3.4.9],
the space for the hydraulic connection is sufficient,
the installation location is of sufficient volume.
Minimum room volume
8-B R-E HE
10-B R-E HE
13-B R-E HE
10-B R HE
13-B R HE
16-B R HE
Minimum room volume EN 378
greater than 6.5 m³
greater than 8.0 m³
greater than 11.0 m³
Minimum clearance
Maintain a side clearance of at least 20 cm to walls and/or objects during the in-
stallation or servicing work.
4.2 Remove front panel
The front panel is secured with a screw at the tension lock to prevent accidental
opening.
Refit screw when mounting front panel.
Remove screw
1
from tension lock at the underside of the unit.
Open the tension lock and remove the front panel.
1