6.7.7 Variable output
Variable
output
The menu is only displayed in the Expert level.
The variable output can be defined for various functions. The scope of the submenu
is displayed depending on the definition.
Parameters Setting
Info
Shows the function of the variable output currently selected.
Circulation
pump
Mode:
Determines if the output is
Off
or if it is controlled time-dependent during DHW loading (
Time
).
Time period
:
Duration of cycle
Pause
:
Off time during a cycle.
Example:
Time period: 15 min
Pause: 5 min
Run time pump: ON = 10 min, OFF = 5 min
Time
programs
In the time program for the timer function, one time cycle is preset for each weekday. The time program
can be adapted individually, the procedure is the same as for the time programs [ch. 6.4.3].
Settings
Determines the function of the variable output.
Off
:
No function, is not controlled.
Circulation pump
:
Output is periodically controlled during the DHW program.
Ext. heating circuit pump
:
Output is controlled in the heating mode of the heat pump.
Timer
:
Output is controlled to time program.
Fault message
:
Output is controlled if a fault occurs in the heat pump.
Cooling operation
:
Output is controlled in the cooling mode of the heat pump.
Compressor operation
:
Output is controlled in compressor operation of the heat pump.
DHW operation
:
Output is controlled during DHW loading.
Continuous voltage
:
Output is controlled when the hydraulic unit is switched on.
Reset
Reset all changes made in menu Variable output to factory settings.