![Weishaupt WWP L 15 ARS Скачать руководство пользователя страница 23](http://html.mh-extra.com/html/weishaupt/wwp-l-15-ars/wwp-l-15-ars_installation-and-operating-instruction_953333023.webp)
4.2 Installing outdoor unit
DANGER
Risk of suffocation due to leaking refrigerant
Leaking refrigerant collects at the base of the unit.
Inhalation may cause suffocation, and even death.
Contact with the skin can cause frostbite.
▶
Do not damage refrigeration circuit.
WARNING
Environmental damage due to leaking refrigerant
Refrigerant contains fluorinated greenhouse gases in accordance with the Kyoto
Protocol and must not be discharged into the atmosphere.
▶
Do not damage refrigeration circuit.
CAUTION
Damage to the unit by tilting
Compressor could be damaged.
▶
When transporting, do not tilt the unit more than 45°.
Observe wind load in accordance with DIN 1055 and protect depending on structural
conditions on site.
Break out openings for condensate outlet
The condensate must be drained from the unit by the shortest route and must be
protected from frost.
▶
Break out pre-cut openings
2
in the condensate pan.
✓
Condensate water can also drain away through these openings.
If the condensate must be drained via the condensate drain
1
only, Weishaupt rec-
ommends trace heating for the condensate pan (accessory).
Installation and operating instruction
Outdoor unit WWP L 15 ARS
4 Installation
83292002 • 1/2014-05 • La
23-55
Содержание WWP L 15 ARS
Страница 1: ...Installation and operating instruction Outdoor unit WWP L 15 ARS 83292002 1 2014 05 ...
Страница 52: ...12 Notes Installation and operating instruction Outdoor unit WWP L 15 ARS 12 Notes 83292002 1 2014 05 La 52 55 ...
Страница 53: ...Installation and operating instruction Outdoor unit WWP L 15 ARS 12 Notes 83292002 1 2014 05 La 53 55 ...