Installation and operating instruction
Oil burner WL40Z-A 1LN
7 Commissioning
83298902 2/2019-05 La
44-112
Adjust P
0
Press [-] key.
Burner drives to operating point P
0
(ignition position).
Press and hold [L/A] key and set P
0
to the same value as P
1
using the [-] or [+]
key.
Check mixing pressure
The mixing pressure in ignition position must be between 2.0 4.5 mbar.
If necessary, adjust mixing pressure via air damper setting [L/A].
Press [-] key.
Burner drives to stage 1 (P
1
).
Press [+] key.
Burner drives to stage 2 (P
9
).