Installation and operating instruction
Oil burner WL30Z-C
7 Commissioning
83297902 3/2019-11 La
47-112
3. Check start behaviour and on/off switch points
Switch off and restart burner.
Check start behaviour
Check on and off switch point stage 2:
excess air phase (CO content) prior to switch over must not be too long,
flame must not fail.
If necessary correct ignition position P
0
.
If necessary correct switch on point P
3
and switch off point P
2
.
If the existing settings have been changed:
re-check start behaviour and on and off switch points.