Installation and operating instruction
Oil burner WL30Z-C
5 Installation
83297902 3/2019-11 La
24-112
5 Installation
5.1 Oil supply
Observe EN 12514-2, DIN 4755, TRÖI and local regulations.
Check conditions for oil pump
Suction resistance
max 0.4 bar
(1
Supply pressure
max 2 bar
(1
Supply temperature
max 60 °C
(1
(1
Measured at the pump.
Check conditions for oil hoses
Length
1200 mm
Oil hose connection
G⅜
Nominal pressure
10 bar
Thermal load
max 100 °C
Connect oil supply
CAUTION
Damage to the oil pump caused by incorrect connection
Mixing up supply and return can damage the oil pump.
Ensure correct connection of oil hoses to the supply and return of the pump.
Fit oil hoses with bracket
4
and grommet
3
to burner.
1
2
3
4
1
Return
2
Supply