![Weishaupt WG20 1-C Z-LN Series Скачать руководство пользователя страница 55](http://html.mh-extra.com/html/weishaupt/wg20-1-c-z-ln-series/wg20-1-c-z-ln-series_manual_953344055.webp)
Installation and operating instruction
Gas burner WG40…/1-A ZM-LN
7 Commissioning
83300002 1/2019-02 La
55-128
9. Optimising the operating points
Check combustion values
Press and hold [G] and optimise combustion values using [–] or [+] key.
Press [+] key.
Next operating point is initiated.
Repeat steps at each operating point until P9 has been reached.
Press [G] and [L/A] keys simultaneously.
The upper operating limit (
bo
) is displayed.
10. Adjust partial load
Press [G] and [L/A] keys simultaneously.
Burner drives to partial load.
The lower operating limit is displayed (
bu
).
Define partial load whilst observing:
data supplied by boiler manufacturer,
burner capacity graph [ch. 3.4.6].
Determine gas throughput, if necessary adjust partial load (
bu
) using [+] key.
Press [G] and [L/A] keys simultaneously.
Combustion manager changes to operating level (
10
).
Combustion manager is programmed.
11. Check start behaviour
Switch off and restart burner.
Check start behaviour and if necessary correct operating point P
0
(ignition pos-
ition).
If the ignition position has been altered:
Re-check start behaviour.
Содержание WG20 1-C Z-LN Series
Страница 1: ...Installation and operating instruction Gas burner WG40 1 A ZM LN 83300002 1 2019 02 ...
Страница 105: ...Installation and operating instruction Gas burner WG40 1 A ZM LN 12 Project planning 83300002 1 2019 02 La 105 128 ...
Страница 124: ...Installation and operating instruction Gas burner WG40 1 A ZM LN 14 Notes 83300002 1 2019 02 La 124 128 14 Notes ...