Installation and operating instruction
Gas burner WG40…/1-A ZM-LN
3 Product description
83300002 1/2019-02 La
12-128
3.3.2 Gas supply
Gas isolating valve
1
The gas isolating valve opens and shuts off the gas supply.
Multifunction assembly
8
The multifunction assembly contains:
Gas filter
Double gas valve
Pressure regulators
Gas filter
2
The gas filter protects the subsequent valve train components from foreign
particles.
Double gas valve
4
The double gas valve opens and shuts off the gas supply.
Pressure regulator
3
The pressure regulator reduces the connection pressure and ensures a constant
setting pressure.
Gas butterfly valve
5
The gas butterfly valve regulates the gas quantity depending on the rating required.
The combustion manager drives the gas butterfly valve via actuator.
Low gas pressure switch/ valve proving gas pressure switch
7
The gas pressure switch monitors the gas connection pressure. If the preset pres-
sure is not achieved, the combustion manager initiates a safety shutdown.
The gas pressure switch also monitors if the gas valves are tight. It signals the
combustion manager if the pressure increases or decreases to an impermissible
level during valve proving.
Valve proving is carried out automatically by the combustion manager:
after every controlled shutdown,
prior to burner start following lockout or power outage.
1. Test phase (function sequence for valve proving valve 1):
Valve 1 closes,
valve 2 closes after a delay,
the gas escapes and the pressure between valve 1 and valve 2 reduces,
both valves remain closed for 8 seconds.
If the pressure increases to above the value set during these 8 seconds, valve 1 is
leaking. The combustion manager initiates a controlled shutdown.
2. Test phase (function sequence for valve proving valve 2):
Valve 1 opens, valve 2 remains closed,
pressure between valve 1 and valve 2 increases,
valve 1 closes again,
both valves remain closed for 16 seconds.
If the pressure decreases to below the value set during these 16 seconds, valve 2
is leaking. The combustion manager initiates a controlled shutdown.