background image

 

© 2022 WEINZIERL ENGINEERING GmbH 

Seite 8/22 

Wireless extension of a KNX line 

 

 

Содержание 5474

Страница 1: ...el 49 8677 916 36 0 E Mail info weinzierl de Web www weinzierl de 2022 WEINZIERL ENGINEERING GmbH Seite 1 22 Compact KNX RF TP coupler with support of KNX Data Security Security Proxy and Segment Coupler KNX RF TP Coupler 673 1 secure Operation and installation manual Art 5474 ...

Страница 2: ...ory default settings 6 3 1 Factory default settings 6 4 Wiring scheme 6 4 1 Line Coupler 7 4 2 Segment Coupler 9 5 KNX Security 10 5 1 Security Proxy 10 6 ETS database 11 6 1 ETS 5 11 6 2 ETS 6 11 6 3 Secure commissioning 11 6 4 Secure group communication 14 6 5 Description 16 6 6 General settings 16 6 7 Routing TP RF 17 6 8 Routing RF TP 19 6 9 Filter Table Security Proxy Tables 21 ...

Страница 3: ... ETS 6 database 2 Installation and connection Mounting can be recessed in the wall and thus almost invisible because the housing has the right size for mounting in a standard flush mounted box When selecting the mounting location the range of the radio devices to be connected to the device must be taken into account Shielding objects e g metal cabinets or interfering transmitters e g computers ele...

Страница 4: ...of the LEDs 1 8 2 2 1 Manual operation TP Briefly pressing button A activates manual operation for mode TP Pressing button A briefly deactivates activates the forwarding of the group telegrams This is indicated by LEDs 1 and 2 Pressing button B briefly deactivates activates the forwarding of the physically addressed telegrams and the broadcast telegrams This is indicated by LEDs 3 and 4 Pressing b...

Страница 5: ... KNX TP is active LEDs 1 and 2 off Manual operation is active Forwarding of group telegrams via KNX TP is not active LEDs 3 and 4 light green Manual operation is active Forwarding of physically addressed telegrams and broadcast telegrams via KNX TP is active LEDs 3 and 4 off Manual operation is active Forwarding of physically addressed telegrams and broadcast telegrams via KNX TP is not active LED...

Страница 6: ...ming button pressed for at least another 6 seconds A short flashing of all LEDs visualizes the successful reset of the device to factory default settings 3 1 Factory default settings In the factory default settings the device has the physical address 15 15 0 Also KNX Data Security is disabled and the initial key FDSK must be used for secure commissioning Routing TP RF Group telegrams Filter Indivi...

Страница 7: ... y 1 15 Thus the device functions as a line coupler The device functions as a line coupler only if its individual address has the form x y 0 The KNX RF TP Coupler 673 1 secure has a filter table and therefore helps to reduce the bus load The filter table supports the extended group address range main groups 0 31 and is automatically generated by the ETS ...

Страница 8: ... 2022 WEINZIERL ENGINEERING GmbH Seite 8 22 Wireless extension of a KNX line ...

Страница 9: ...t Coupler The individual address of the KNX RF TP Coupler 673 1 secure corresponds to the form x y z x y 1 15 z 1 255 Thus the device functions as a segment coupler The device functions as a segment coupler only if its individual address has the form x y z ...

Страница 10: ...ity can also be used in existing KNX systems and with non secure KNX TP devices KNX Data Security describes the encryption on telegram level This means that the telegrams on the twisted pair bus or via RF radio frequency are also encrypted Encrypted telegrams are longer than the previously used unencrypted ones For secure programming via the bus it is therefore necessary that the interface used e ...

Страница 11: ...elegrams 6 1 ETS 5 The ETS 5 database supports only KNX Data Security The functionality of Security Proxy and Segment Coupler is not supported 6 2 ETS 6 The ETS 6 database supports KNX Data Security as well as the functionality of Security Proxy and Segment Coupler 6 3 Secure commissioning If the first product is inserted into a project with KNX Security the ETS prompts you to enter a project pass...

Страница 12: ...el Reports Project Security This initial key is required to safely put a device into operation from the start Even if the ETS download is recorded by a third party the third party has no access to the secured devices afterwards During the first secure download the initial key is replaced by the ETS with a new key that is generated individually for each device This prevents persons or devices who m...

Страница 13: ... changed here as well as the retransmitter mode repeater mode can be de activated in the device In this mode the received telegrams are retransmitted to increase the RF range With Subnet Isolation it can be set whether transmission and point to point communication is allowed into the subnet It is recommended to set this to Automatic Thus the telegrams are forwarded or filtered as configured in the...

Страница 14: ...e overview Properties appears on the right side of the ETS window Under Properties menu item Settings the domain address of the line can be changed 6 4 Secure group communication Each object of the device can communicate either encrypted or unencrypted The encryption is set under Security in the properties of the used group address ...

Страница 15: ... enable all devices to communicate with a secure group address the keys must be known to all Therefore a download must be made into all devices that use this group address when a key is created or changed A key is changed by the ETS e g when the encryption of a group address is switched off and on again Telegrams from the bus that do not address the KNX RF TP Coupler 673 1 secure as a device are f...

Страница 16: ...ows the device description and the corresponding connection diagram 6 6 General settings Device name 30 characters Any name can be assigned to the KNX RF TP Coupler 673 1 secure The device name should be meaningful e g Living room EG This helps the clarity in the ETS project ...

Страница 17: ...ilable Disabled Enabled with time limit 1 min Enabled with time limit 10 min Enabled with time limit 30 min Enabled without time limit The activated manual operation can reduce the security of the installation 6 7 Routing TP RF Group telegrams The following settings are possible Block No group telegram is forwarded to the RF line Route All group telegrams are forwarded to the RF line regardless of...

Страница 18: ...grams The following settings are possible Block No received system broadcast telegram is forwarded to the RF line Route All received system broadcast telegrams are forwarded to the RF line Broadcast telegrams The following settings are possible Block No received broadcast telegram is forwarded to the RF line Route All received broadcast telegrams are forwarded to the RF line Acknowledge ACK of gro...

Страница 19: ...er the received group telegram is forwarded to the TP line The setting Route should only be used for test purposes Individual addressed telegrams The following settings are possible Block No individual addressed telegram is forwarded to the TP line Route All individual addressed telegrams are forwarded to the TP line Filter The destination address is used to check whether the received individual a...

Страница 20: ...arded group telegram will be not repeated in case of an error in the TP line Enabled The forwarded group telegram will be repeated up to three times in case of an error Repetition of individual addressed telegrams The following settings are possible Disabled The forwarded individual addressed telegram will be not repeated in the TP line in case of an error Enabled The forwarded individual addresse...

Страница 21: ...to be forwarded via the coupler are included in the filter table for this purpose The content of the filter table can be displayed via the preview Also the security proxy tables are displayed here The filter table can be extended by manually adding group addresses For this purpose Pass through Line Coupler must be activated in the properties window of the corresponding group address ...

Страница 22: ...allations the relevant guidelines regulations and standards of the respective country are to be considered Product database for ETS 6 www weinzierl de en products 673 1 ets6 Data sheet www weinzierl de en products 673 1 datasheet CE Declaration www weinzierl de en products 673 1 ce declaration WEINZIERL ENGINEERING GmbH Achatz 3 4 84508 Burgkirchen an der Alz GERMANY Tel 49 8677 916 36 0 E Mail in...

Отзывы: