background image

Part number 550-141-858/0107

4

WMZV

 

Zone Valve Controllers

Wiring

Diagram 1

Typical WMZV-4

Sequence of operation:

When a zone thermostat closes,
the WMZV-4 activates its zone
valve. The green light for the zone
comes on.

When the zone valve end switch
closes, it causes the red light to
come on, indicating the zone
valve is fully open.

The WMZV-4 then activates the
end switch relay and turns on the
yellow light to indicate the isolated
contacts are now closed. This
allows the boiler or circulator to
operate device(s) wired to X-X.

If the 

PRIORITY ZONE

SWITCH

 is in the 

ON

 position,

the WMZV-4 will not activate
zones 2, 3 or 4 while the priority
zone calls for heat.

All wiring must be installed in accordance with:

U.S.A.

 — National Electrical Code and any other national, state or local code

requirements. Wiring must be N.E.C. Class 1.

Canada

 — C.S.A. C22.1 Canadian Electrical Code Part 1 and any other

national, provincial or local code requirements. Wiring must be C.S.A.
C22.1 C.E.C. Part 1.

Electrical shock hazard — Disconnect power before installing or servicing.
Can cause severe personal injury, death or substantial property damage if
ignored.

This controller will 

NOT

 function with White-Rodgers 1311 and 1361 zone

valves.

Install all zone valves per valve
manufacturer’s instructions.

Содержание WMZV-4

Страница 1: ... 4 Four zone controller WMZV 6 Six zone controller This manual must only be used by a qualified heating installer service technician Failure to comply could result in severe personal injury death or substantial property damage Zone Valve Controllers ...

Страница 2: ...nt but not related to personal injury or property damage Electrical shock hazard Disconnect power before installing or servicing Can cause severe personal injury death or substantial property damage if ignored All wiring must be installed in accordance with U S A National Electrical Code and any other national state or local code requirements Wiring must be N E C Class 1 Canada C S A C22 1 Canadia...

Страница 3: ... zone valves including Taco Superior Erie Honeywell B G SPARCO and most other motorized and heat motor type valves 6 Switchable priority improves versatility 7 Plug in replaceable isolated contact relay 8 24 VAC constant power for 5 wire zone valves such as Honeywell VC Series 40 and 80 valves 9 Isolated end switch terminals X X 10 Powerful transformer 40 VA on WMZV 4 75 VA on WMZV 6 11 Galvanized...

Страница 4: ...RIORITY ZONE SWITCH is in the ON position the WMZV 4 will not activate zones 2 3 or 4 while the priority zone calls for heat All wiring must be installed in accordance with U S A National Electrical Code and any other national state or local code requirements Wiring must be N E C Class 1 Canada C S A C22 1 Canadian Electrical Code Part 1 and any other national provincial or local code requirements...

Отзывы: