3

Instruction manual

WMZV features

The printed circuit design of these controllers eliminates most field wiring

needed for zone valves, making their installation 

easier 

and 

quicker

.

Built-in priority zone means 

no other controllers are needed

 to provide

priority heating for indirect water heaters including 

Weil-McLain Plus

Indirect-Fired Water Heaters

.

1.

Double-sided printed circuit
board construction is 100%
factory tested.

2.

Clearly marked terminals with
quick-connect screwless clamps.

3.

Plug-in replacement priority
relay.

4.

LED diagnostic lights for easy
troubleshooting.

5.

Will operate four or six 24-volt
(powered open, or powered
closed) zone valves including:
Taco, Superior, Erie,
Honeywell, B&G, SPARCO
and most other motorized and
heat motor type valves.

6.

Switchable priority improves
versatility.

7.

Plug-in replaceable isolated-
contact relay.

8.

24 VAC constant power for
5-wire zone valves (such as
Honeywell VC Series 40 and 80
valves).

9.

Isolated end switch terminals,

X–X

.

10.

Powerful transformer (40 VA on
WMZV-4, 75 VA on WMZV-
6).

11.

Galvanized steel enclosure with
enamel-painted cover.

Specifications

Weil-McLain

model

number

Number

of zones

(see Note)

Transformer

output at

24 VAC

End switch

contact rating

Enclosure

dimensions

(L x H x D)

WMZV-4

3 + 1

40 VA

1/3 HP @ 120 VAC

9" x 7" x 2¾"

WMZV-6

5 + 1

75 VA

1/3 HP @ 120 VAC

11¼" x 7" x 2¾"

Note: Check zone valve specifications for required VA per valve.

Do not use digital thermostats unless recommended by zone valve manufacturer.
Thermostat current set from zone valve manufacturer.

Содержание WMZV-4

Страница 1: ... 4 Four zone controller WMZV 6 Six zone controller This manual must only be used by a qualified heating installer service technician Failure to comply could result in severe personal injury death or substantial property damage Zone Valve Controllers ...

Страница 2: ...nt but not related to personal injury or property damage Electrical shock hazard Disconnect power before installing or servicing Can cause severe personal injury death or substantial property damage if ignored All wiring must be installed in accordance with U S A National Electrical Code and any other national state or local code requirements Wiring must be N E C Class 1 Canada C S A C22 1 Canadia...

Страница 3: ... zone valves including Taco Superior Erie Honeywell B G SPARCO and most other motorized and heat motor type valves 6 Switchable priority improves versatility 7 Plug in replaceable isolated contact relay 8 24 VAC constant power for 5 wire zone valves such as Honeywell VC Series 40 and 80 valves 9 Isolated end switch terminals X X 10 Powerful transformer 40 VA on WMZV 4 75 VA on WMZV 6 11 Galvanized...

Страница 4: ...RIORITY ZONE SWITCH is in the ON position the WMZV 4 will not activate zones 2 3 or 4 while the priority zone calls for heat All wiring must be installed in accordance with U S A National Electrical Code and any other national state or local code requirements Wiring must be N E C Class 1 Canada C S A C22 1 Canadian Electrical Code Part 1 and any other national provincial or local code requirements...

Отзывы: