Vent termination requirements
Figure 24
The vent termination must be located to meet all requirements below (also applies to vertical vent terminations). The minimum distance from
adjacent public walkways, adjacent buildings, openable windows and building in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or
the Natural Gas and Propane Installation Code, CAN/CSA B149.1. The vent termination clearances below are for U.S.A., for Canadian vent
termination clearances please refer to the requirements of CAN/CSA B149.1 Natural Gas and Propane Installation Code. Consideration
should be given to avoid possible damage caused by vent plumes and condensate when choosing a venting confi guration and location.
Maintain a minimum clearance of 4 ft. (1.22m) horizontally from, and in no case above or below, unless a 4 ft. (1.22m) horizontal distance
is maintained, from electrical meters, gas meters, regulators, and relief equipment.
Part number 550-100-191/0917
26
®
g
as-fired water boiler —
70/110/155
Boiler Manual