CHAPTER 3 - INSTALLATION AND CONNECTION
24
English
3.2.7 Control
and Signal
Connections
EMI - Electronic Interference
The Soft-Starter SSW-07 is developed to be used in industrial
systems (Class A) according to Standard EN60947-4-2.
It’s necessary to have a distance of 0.25 m (10 in) between the
Soft- Starter SSW-07 control cables and motor cables.
Example: PLC wiring, temperature controllers, thermocouple cables, etc.
Grounding of the Motor frame
Always ground the motor frame. The Soft-Starter SSW-07 output
wiring to the motor must be installed separately from the input wiring
as well as from the control and signal wiring.
The control connections (digital inputs and relay outputs) are made
through the terminals (refer to figure 3.9).
Terminal
Description
Specifications
Torque Nm
(in lb)
A1
Electronics Supply
Voltage: 110 to 240 Vac (-15 % to +10 %)
(models from 17 A to 200 A)
110 to 130 Vac or 208 to 240 Vac
(-15 % to 10 %) (models from 255 A
to 412 A).
0.5 (4.5)
A2
Grounding
Only for the 255 to 412 A models
Terminal
Factory Default
Specifications
DI1
Starts/Stops Motor
3 isolated digital inputs
Voltage: 110 to 240 Vac (-15 % to +10 %)
Current: 2 mA Max.
DI2
Fault reset
DI3
Fault reset
13
Relay 1 output - Operation
Contact capacity:
Voltage: 250 Vac
Current: 1 A
14/23 Relay common point
24
Relay 2 output - Full voltage
Table 3.9 -
Description of the control connector pins
Figure 3.9 -
Control terminals of the Soft-Starter SSW-07
NOTE!
It is recommended to use shielded cables for the Dix inputs when
using long cables (above 30 m) in noisy environments. The metallic
shield and A2 must be grounded.