![WEG MOD1 Series Скачать руководство пользователя страница 38](http://html1.mh-extra.com/html/weg/mod1-series/mod1-series_user-manual_950809038.webp)
Technical Data
MOD1...MOD7 | 6-1
6
6 TECHNICAL DATA
Operating Temperature:
0 °C to 45 °C (32 °F to 113 °F).
Air relative humidity: 5 % to 90 % non-condensing.
Degree of Protection:
IP20.
Pollution Degree:
2 (according to EN50178 and UL508C), with non-conductive pollution.
Altitude:
1000 m (3,300 ft). Above 1000 m to 4000 m (3,300 ft to 13,200 ft), the output current must be derated by 1 %
for every 100 m (328 ft) above 1000 m (3,300 ft).
Environment with pollution degree 2 (as per EN50178 and UL508C.
Digital Outputs:
PNP outputs.
Recommended voltage V+: 24 V.
Maximum voltage V+: 28.8 V.
Maximum current of each output: 500 mA.
Digital Inputs:
Bidirectional inputs.
Maximum input voltage: 28.8 V.
High level: Vin ≥ 10 V.
Low level: Vin ≤ 3 V.
Consumption at 24 V: 10 mA.
Insulation voltage: 500 V.