55
CHAPTER 6 - DETAILED PARAMETER DESCRIPTION
Range
[Factory Setting]
Parameter
Description / Notes
P000
0 to 999
Access
[ 0 ]
Parameter
1
6.3.1 Access and Read Only Parameters - P000 to P099
P002
0 to 999
Frequency
[ - ]
Proportional Value
0.01 (<100.0);
0.1 (<1000);
1 (>99.9)
P003
0 to 1.5 x Inom
Output Current
[ - ]
(Motor)
0.1A
P004
0 to 424V
DC Link Voltage
[ - ]
1V
Releases the access to change the parameter values.
The password is 5.
The use of the password is always active.
Indicates the value of P208 x P005.
In case of different scales and units, use P208.
Indicates the inverter output current in ampères. (A).
Indicates the inverter DC Link voltage in volts (V).
P005
0 to 300 Hz
Output Frequency
[ - ]
(Motor)
0.1Hz (<100 Hz);
1Hz (>99.9 Hz)
Indicates the inverter output frequency in Hertz (Hz).
P007
0 to 240V
Output Voltage
[ - ]
1V
Indicates the inverter output voltage in volts (V).
P008
25 to 110
o
C
Heatsink
[ - ]
Temperature
1
o
C
Indicates the current power at the heatsink in Celsius
degrees (°C).
The inverter overtemperature protection (E04) acts when
heatsink temperature reaches 103ºC:
P014
00 to 41
Last Fault
[ - ]
-
Indicates the code of the last occured fault.
Section 7.1 shows a list of possible faults, their code
numbers and possible causes.
P023
x.yz
Software Version
[ - ]
Indicates the software version installed in the DSP
memory located on the control board.