Parameter
Description
Range of values
Decimal
places
Net Id
Size
Qty mapped
words
C5.8.11.1
Mode
1001
enum
1
0 = Fault F112 and F120
1 = Alarm A112 and A120
C5.8.12
Ch4 Overtemperature
C5.8.12.1
Mode
978
enum
1
0 = Fault F104
1 = Alarm A104
2 = F104 and A104
C5.8.12.2
Fault Level
0 to 250
◦
C
0
979
8bit
1
C5.8.12.3
Alarm Level
0 to 250
◦
C
0
980
8bit
1
C5.8.12.4
Alarm Reset
0 to 250
◦
C
0
981
8bit
1
C5.8.13
Ch5 Installed Sensor
C5.8.13.1
Mode
1010
enum
1
0 = Off
1 = On
2 = On Stator
C5.8.14
Ch5 Sensor Fault
C5.8.14.1
Mode
1002
enum
1
0 = Fault F113 and F121
1 = Alarm A113 and A121
C5.8.15
Ch5 Overtemperature
C5.8.15.1
Mode
982
enum
1
0 = Fault F105
1 = Alarm A105
2 = F105 and A105
C5.8.15.2
Fault Level
0 to 250
◦
C
0
983
8bit
1
C5.8.15.3
Alarm Level
0 to 250
◦
C
0
984
8bit
1
C5.8.15.4
Alarm Reset
0 to 250
◦
C
0
985
8bit
1
C5.8.16
Ch6 Installed Sensor
C5.8.16.1
Mode
1011
enum
1
0 = Off
1 = On
2 = On Stator
C5.8.17
Ch6 Sensor Fault
C5.8.17.1
Mode
1003
enum
1
0 = Fault F114 and F122
1 = Alarm A114 and A122
C5.8.18
Ch6 Overtemperature
C5.8.18.1
Mode
986
enum
1
0 = Fault F106
1 = Alarm A106
2 = F106 and A106
C5.8.18.2
Fault Level
0 to 250
◦
C
0
987
8bit
1
C5.8.18.3
Alarm Level
0 to 250
◦
C
0
988
8bit
1
C5.8.18.4
Alarm Reset
0 to 250
◦
C
0
989
8bit
1
C5.9
Motor Thermal Class
C5.9.1
Programming Mode
934
enum
1
SSW900
|
50