C CONFIGURATIONS
Description:
It sets the number of write words for data communication (outputs for master), from the first word on.
C8.1.2 Data Write
C8.1.2.3 Slot 2 1st Word
Range:
1 ... 20
Default:
11
Properties:
Stopped
Description:
It sets the index of the first programmable write word for data communication (outputs for master).
C8.1.2 Data Write
C8.1.2.4 Slot 2 Quantity
Range:
1 ... 20
Default:
1
Properties:
Stopped
Description:
It sets the number of write words for data communication (outputs for master), from the first word on.
C8.1.2 Data Write
C8.1.2.5 Update Delay
Range:
0.0 ... 999.9 s
Default:
0.0
Properties:
Description:
Whenever there is a transition from offline (without cyclic data) to online (with cyclic write data), the data received via
communication networks (write words) is ignored during this programmed time, remaining in the state it was before
the beginning of the reception.
t(s)
0
Updates
writing words
Not updated
writing words
Delay
Online
Offline
Online
Figure 5.2:
Delay in the update of the I/O words.
C8.1.2 Data Write
C8.1.2.6 Word #1
C8.1.2.6 to C8.1.2.25
C8.1.2 Data Write
C8.1.2.25 Word #20
Range:
0 ... 65535
Default:
0
Properties:
Stopped
Description:
Select the net address of other parameter, which content will be available as writing data for fieldbus interfaces
(outputs: received from master).
SSW900 | 17