S STATUS
Description:
Command word of all sources of the SSW. The RUN/STOP and JOG commands of the sources which are not active
will be reset.
.5 Slot1
Control word via any communication accessory connected to Slot 1.
.6 Slot2
Command word via any communication accessory connected to Slot 2.
Bit
Value/Description
Bit 0
Start/Stop
0
: stopping by ramp.
1
: starting by ramp.
Bit 1
Gener. Enabled
0
: general disable.
1
: general enable.
Bit 2
JOG
0
: no JOG.
1
: with JOG.
Bit 3
FWD/REV
0
: clockwise CW.
1
: counterclockwise CWW.
Bit 4
LOC/REM
0
: local.
1
: remote.
Bit 5 … 6
Reserved
Bit 7
Reset
0
→
1
: execute fault reset (if a fault is active).
Note: Only in the 0 to 1 transition command.
Bit 8 … 15
Reserved
✓
NOTE!
If the RUN/STOP and JOG commands are by a certain source and it is active, only these commands
can be viewed in S5.2. For security reasons, all the other commands of the other sources which are
not active will be reset.
S5.3 Value for Outputs
.1 DO Value
0 ... 15 Bit
Description:
Value for digital and analog outputs via serial communication.
.1 DO Value
Value for the digital outputs via network interfaces.
Bit
Value/Description
Bit 0
DO1
0
: Inactive.
1
: Active.
Bit 1
DO2
0
: Inactive.
1
: Active.
Bit 2
DO3
0
: Inactive.
1
: Active.
Bit 3 … 15
Reserved
S5.3.2 Value for AO
.1 AO in LSB
0 ... 1023
Description:
Value for the analog output via network interfaces.
.1 AO in LSB
Value, Least Significant Bit, for the analog output via network interfaces: 0...1023. 0=0% e 1023=100%.
SSW900 | 13