LV-HUB  V2.01   14/06/2022 

 Low Voltage CAN HUB Dimensions 

 
 

 

Weight:      

Kg: 8   

 

                            

 
 

 

 
 

 

Control Logic and Protection Limit 

The inverter, if applicable, must be set with the below restrictions in addition to the BMS 

control logic.   

MAX CURRENT WITH BUS BAR 

 

                  

*

 

Please refer to the above table according to the number of clusters and parallels applicable to the system. 

 

1.

 

The charge current will be limited to zero Amps when the single module voltage has been reached 56.8V. 

2.

 

The discharge current will be limited to zero Amps when the single module voltage has been discharged to 50.4V. 

3.

 

The battery system will communicate with the inverter to limit the current. 

4.

 

Each Battery Module will be protected by the same logic separately as per single module protection concept. 

5.

 

If some modules, individually, reach any fault status, the single module will protect and disconnect from 
the system in less than 3 seconds. 

6.

 

The current limit must be adjusted according to the real active batteries in system to restore the normal function. 

7.

 

If the cluster is not balanced, the current limitation set from the HUB to the inverter will be sent to manage 
the rest of active modules and clusters.  At the same time, the imbalanced modules or cluster will equalize 
in standby mode and will reconnect once in the normal range. 

8.

 

If more than two batteries in one cluster are in protection mode, the entire cluster will protect by shutting down. 

9.

 

If there are more than two clusters in protection mode, the full system will be protected. 

10.

 

The battery sends information to the inverter to limit the charge/discharge current to zero Amps if the 
battery is detecting an over current. 

11.

 

The protection built into the BMS will automatically disconnect the battery when it detects excess values. 
The BMS will attempt to reconnect up to three times to check if the excess values have returned to within 
the permitted range. After three attempts to reconnect, the BMS will not attempt any further 
reconnections. The Battery Module can be restarted using the module power switch and run button, 
however, if the external fault condition which caused the Battery Module to shut down is not rectified, the 
battery will continue to enter the shutdown mode. 

12.

 

If the current of one cluster is larger than the current limit, the battery system will send a warning in 
accordance with the single module BMS logic. 

 

Modules           Clusters

1

2

3

4

5

6

7

1

100

196

288

376

460

540

616

2

196

376

540

688

820

936

1036

3

288

540

756

936

1080

1188

1260

4

376

688

936

1120

1240

1296

1400

5

460

820

1080

1240

1300

1500

1750

6

540

936

1188

1296

1500

1800

2100

7

616

1036

1260

1400

1750

2100

2450

8

688

1120

1296

1600

2000

2400

2800

9

756

1188

1350

1800

2250

2700

3150

10

820

1240

1500

2000

2500

3000

3500

11

880

1276

1650

2200

2750

3300

3850

12

936

1296

1800

2400

3000

3600

4200

13

988

1300

1950

2600

3250

3900

4550

14

1036

1400

2100

2800

3500

4200

4900

15

1080

1500

2250

3000

3750

4500

5250

 

Содержание LV-HUB GEN-02

Страница 1: ...LV HUB V2 01 14 06 2022 Installation and User Manual LOW VOLTAGE HUB VALID FOR 4K4 PRO and 5K3 LV HV This Manual Is not Valid for installation with 5K3 XP battery module LV HUB GEN 02...

Страница 2: ...TION This device can accumulate parasite current Do not touch the B and B terminals Always check the B and B terminals with a voltmeter Always ensure that there are ZERO volts present on the terminals...

Страница 3: ...by your local installer You can always contact WeCo for additional information on the upgrade procedure Preface Thank you for choosing our product We will provide you with a high quality product as we...

Страница 4: ...in the range of 45 58V that can be provided directly from the common LV bus bar that connect all the cluster using the provided cables Information in this Manual About this Manual Only trained and au...

Страница 5: ...each cluster must have the same Voltage and Firmware All stack configurations must use the WeCo Bus Bar Each cluster must have the same number of battery packs This BMS BMU Master Hub is mandatory whe...

Страница 6: ...he Above Models of batteries the LV HUB GEN 2 can manage a maximum of 7 clusters composed of a maximum of 8 modules each ATTENTION The batteries BMS must UPGRADE the firmware BAT_HUB_V448 for HUB appl...

Страница 7: ...Cluster CAN from last master of the system F OPERATOR PORT OPERATOR PORT FOR RS232 USB converter G INLET 48 Vdc Connector for power input to connect to the bus bar 5A fuse inside H ON OFF SWITCH Inter...

Страница 8: ...ntire cluster will protect by shutting down 9 If there are more than two clusters in protection mode the full system will beprotected 10 The battery sends information to the inverter to limit the char...

Страница 9: ...CTIONS BELOW Special BUS Bar for Parallel Configuration MODULES INTERCONECTION BUS BAR MODEL ACCESSORY 4K4 PRO BUSBAR 5K3LVHV or XP BUSBAR ATTENTION BUS BARS ARE MANDATORY FOR STACK SYSTEM WITHIN 300A...

Страница 10: ...nected the HUB from the CAN B PORT to the CAN INPUT PORT of the HUB 7 The Connection of the power cables between HUBs must be executed in accordance with the previous instruction 8 The HUB can be powe...

Страница 11: ...th the INVERT CAN PORT follow the PIN OUT provided by the Inverter manufacturer for CAN L CAN H 7 Set the cluster batteries DIP switch according to the parallel configuration more detail checks the 4k...

Страница 12: ...LV HUB V2 01 14 06 2022 CONNECTING WITH THE BATTERY LAUNCH THE FW UPGRADE...

Страница 13: ...batteries in the group FOLLOW the DIP address chart below see picture DIP ADDRESS CHART CLUSTER 01 DIP ADDRESS CHART CLUSTER 02 to 5 WARNING Only the first batteries of each cluster must be set follo...

Страница 14: ...IP SETTING FOR 4K4 PRO ATTENTION It is important to restart the batteries after any DIP setting to complete the setup of each single module CLUSTE R ID 01 CLUSTER ID 02 CLUSTER ID 03 CLUSTER ID 04 CLU...

Страница 15: ...r connection to the HUB PORT CAN INPUT CLUSTERS DIP SETTING FOR 5K3 LV HV ATTENTION It is important to restart the batteries after any DIP setting to complete the set up of each single module CLUSTER...

Страница 16: ...not aligned with the others the installer must clear the imbalance by acting individually on each module When all of the three sections are in Green Status will be possible to proceed to the next ste...

Страница 17: ...ll highlight the problem and to proceed it will be necessary to clear any error SYSTEM OVERVIEW By selecting the WE HUB icon from the software after plugging the RS232 converter on the Cluster Number...

Страница 18: ...TENTION Each cluster must be equipped with an isolator to individually disconnect circuit breaker the battery tower from the parallel bus bar in accordance with local regulations Master Inverter NEGAT...

Страница 19: ...omposed of 5 clusters of 5 batteries each Can be composed of 5 clusters of max 8 batteries each SUB n SUB 1 MASTER CAN BMS INVERTER CIRCUIT BREAKER Positive and Negative According to local electrical...

Страница 20: ...equipped with an isolator to individually disconnect circuit breaker the battery tower from the parallel bus bar in accordance with local regulations Master Inverter NEGATIVE POWER CABLES 2X50 75mm PO...

Страница 21: ...composed of 5 clusters of 8 batteries each 5K3 LVHV not valid for 5K3 XP SUB n SUB 1 MASTER CAN BMS INVERTER CIRCUIT BREAKER Positive and Negative According to local electrical codes POWER LINE MAX 6...

Страница 22: ...LV HUB V2 01 14 06 2022 DIP SEQUENCE VALID FOR THE CLUSTER WITH ID 1 4K4PRO and 5K3 LV HV DIP SEQUENCE VALID FOR THE CLUSTERS WITH ID 2 5 4K4PRO and 5K3 LV HV...

Страница 23: ...Icon 7 Turn on the HUB by setting the rocker switch to 1 ON 8 From the main page select the COM PORT and Press CONNECT 9 Once the LED lights will turn ON it will be possible to program the HUB PS it...

Страница 24: ...LV HUB V2 01 14 06 2022 Access the Software using the password 1010 press OPERATOR ACCESS Select HUB SETTING tab Select the COM PORT and press CONNECT...

Страница 25: ...Press Search Hub Firmware and upload the Latest LV HUB FW At the date of the publication of this manual the most recent FW is Press OK to Upload the FW and wait for the Upgrade process to be completed...

Страница 26: ...rm As last step it is mandatory to select the inverter protocol turn on the inverter to enable the communication between LV HUB and Inverter if the Inverter is not active or the communication cable BM...